Technical data

Chapter 7 Analog output modules Manual VIPA System 200V
7-10 HB97E - SM - Rev. 09/19
Electrical data VIPA 232-1BD30
Number of output channels 4
Length of cable: shielded 200m
Supply voltage DC 24V
- Inverse polarity protection yes
Potential separation
- between channels / backplane bus yes
- between channel / power supply of
the electronic
yes
- between the channels no
- channels/load voltage L+ yes
Permitted potential difference
- between the inputs and
M
INTERNAL
(U
ISO
)
DC 75V / AC 60V
Isolation proofed with DC 500V
Current consumption
- via backplane bus 60mA
- from load voltage L+ (without load) 100mA
Power dissipation of the module 2.7W
Analog value calculation output channels
Resolution (incl. Overdrive region)
±10V 11bit + sign
0...10V 11bit
Cycle time (all channels)
700µs
Settling time
- impedance load 1.5ms
- capacitive load 3.0ms
- inductive load -
Suppression of interference, limits of error output channels
Crosstalk between the outputs > 40dB
Operational limit (in the entire temperature range, referring to output range)
Measuring range Tolerance
Voltage output ±10V ±0.2%
0...10V ±0.4%
Basic error limit (operational limit at 25°C, referring to output range)
Measuring range Tolerance
Voltage output ±10V ±0.1%
0...10V ±0.2%
Temperature error
(with reference to the output range)
±0.01%/K
Linearity error
(with reference to the output range)
±0.05%
Repeatability (in steady state at 25°C
referred to the output range)
±0.05%
Output ripple;
range 0 to 50kHz
(referred to output range)
±0.05%
continued ...