Technical data

Chapter 6 Analog input modules Manual VIPA System 200V
6-66 HB97E - SM - Rev. 09/19
... continue
Limits of error VIPA 231-1FD00
Operational limit (in the entire temperature range with
reference to the input range)
- Voltage input ±400mV ±0.4%
- Voltage input ±4V ±0.2%
- Voltage input ±10V ±0.2%
- Current input ±20mA ±0.2%
- Current input 4...20mA
±0.5%
Basic error (Operational limit at 25°C referred to the input
range)
- Voltage input ±400mV ±0.3%
- Voltage input ±4V ±0.1%
- Voltage input ±10V ±0.1%
- Current input ±20mA ±0.1%
- Current input 4...20mA
±0.3%
Temperature error (reference to the input range)
- via current measurement
±0.005%/K
Linearity error (with reference to the input range)
±0.02%
Repeatability (in steady state at 25°C, reference to the
input range)
±0.05%
Status, Interrupts, Diagnostics
Interrupts
- Process interrupt when limit has been exceeded parameterizable
- Diagnostic interrupt parameterizable
Diagnostic functions
- Channel error display red LED (F0 ... F3)
- Diagnostic information read-out possible
Data for selecting a sensor
Input range Input resistance
- Voltage ±400mV, ±4V, ±10V 10M
- Current 4...20mA, ±20mA 57
Maximum input voltage for voltage input (destruction limit) max. 15V
Maximum input current for current input (destruction limit) max. 50mA
Connection of the sensor
- for measuring voltage possible
- for measuring current
via 2-wire transmitter
possible (via external supply)
see wiring diagram 3
via 4-wire transmitter possible