Technical data
Manual VIPA System 200V Chapter 2 Assembly and installation guidelines
HB97E - SM - Rev. 09/19 2-5
Assembly
Please follow these rules during the assembly!
• Turn off the power supply before you insert or remove any modules!
• Make sure that a clearance of at least 60mm exists above and 80mm
below the middle of the bus rail.
80 mm
60 mm
• Every row must be completed from left to right and it has to start with a
header module (PC, CPU, and bus coupler).
12
4
3
• Modules are to install adjacent to each other. Gaps are not permitted
between the modules since this would interrupt the backplane bus.
• A module is only installed properly and connected electrically when it
has clicked into place with an audible click.
• Plug-in locations after the last module may remain unoccupied.
Note!
A maximum of 32 modules can be connected at the back plane bus. Take
attention that here the maximum sum current of 3.5A is not exceeded.
[1] Header module,
like PC, CPU, bus
coupler, if double
width
[2] Header module
(single width)
[3] Peripheral module
[4] Guide rails