Technical data

Manual VIPA System 200V Chapter 2 Assembly and installation guidelines
HB97E - SM - Rev. 09/19 2-5
Assembly
Please follow these rules during the assembly!
Turn off the power supply before you insert or remove any modules!
Make sure that a clearance of at least 60mm exists above and 80mm
below the middle of the bus rail.
80 mm
60 mm
Every row must be completed from left to right and it has to start with a
header module (PC, CPU, and bus coupler).
12
4
3
Modules are to install adjacent to each other. Gaps are not permitted
between the modules since this would interrupt the backplane bus.
A module is only installed properly and connected electrically when it
has clicked into place with an audible click.
Plug-in locations after the last module may remain unoccupied.
Note!
A maximum of 32 modules can be connected at the back plane bus. Take
attention that here the maximum sum current of 3.5A is not exceeded.
[1] Header module,
like PC, CPU, bus
coupler, if double
width
[2] Header module
(single width)
[3] Peripheral module
[4] Guide rails