Technical data

Manual VIPA System 200V Chapter 6 Analog input modules
HB97E - SM - Rev. 09/19 6-59
Analog values are represented as a two’s complement value.
Numeric notation:
Byte Bit 7 ... Bit 0
0 Bit 7 ... 0: binary measured value
1 Bit 6 ... 0: binary measured value
Bit 7: sign
0 positive
1 negative
+/- 10V
Voltage Decimal Hex
-10V -27648 9400
-5V -13824 CA00
0V 0 0
5V 13824 3600
10V 27648 6C00
+/-4V
Voltage Decimal Hex
-4V -27648 9400
0V 0 0
4V 27648 6C00
+/-400mV
Voltage Decimal Hex
-400mV -27648 9400
0V 0 0
400mV 27648 6C00
4....20mA
Current Decimal Hex
4mA 0 0
12mA 13824 3600
20mA 27648 6C00
+/- 20mA
Current Decimal Hex
-20mA -27648 9400
-10mA -13824 CA00
0mA 0 0
10mA 13824 3600
20mA 27648 6C00
Numeric notation
in S7 from
Siemens
Formulas for the calculation:
10
27648
U
Value =
,
27648
10
= ValueU
U: voltage, Value: decimal value
Formulas for the calculation:
4
27648
U
Value =
,
27648
4
= ValueU
U: voltage, Value: decimal value
Formulas for the calculation:
400
27648
U
Value =
,
27648
400
= ValueU
U: voltage, Value: decimal value
Formulas for the calculation:
16
4
27648
=
I
Value
,
4
27648
16
+= ValueI
I: current, Value: decimal value
Formulas for the calculation:
20
27648
I
Value =
,
27648
20
= ValueI
I: current, Value: decimal value