Technical data
Chapter 6 Analog input modules Manual VIPA System 200V
6-40 HB97E - SM - Rev. 09/19
Measured
value in
mA
Units
Binary measured
value
T E Ü Range
24.0 2560 0 1 0 1 0 0 0 0 0 0 0 0 0 0 0 0 overdrive region
20.016 2049 0 1 0 0 0 0 0 0 0 0 0 0 1 0 0 0
20.0 2048 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 nominal range
19.98 2047 0 0 1 1 1 1 1 1 1 1 1 1 1 0 0 0
12.0 1024 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0
8.0 512 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0
6.0 256 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0
5.0 128 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0
4.016 2 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0
4.008 1 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0
4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
3.984 -2 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 Underdrive region
3.0 -128 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0
2.0 -256 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0
1.0 -384 1 1 1 1 0 1 0 0 0 0 0 0 0 0 0 0
0.0 -512 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0
Electrical data VIPA 231-1BD60
Number of inputs 4 individually isolated
Current measuring range 4 ... 20mA
Input filter time delay 3ms
Input resistance
20Ω
Power supply 5V via backplane bus
Current consumption 280mA via backplane bus
Isolation yes, every channel separately,
isolation tested at 500Vrms
Status indicators via LEDs on the front
Programming specifications
Input data 8byte (1 word per channel)
Output data -
Parameter data -
Diagnostic data -
Process alarm data -
Dimensions and weight
Dimensions (WxHxD) 25.4x76x88mm
Weight 120g
Numeric notation
in Siemens
S5 format