Technical data

Manual VIPA System 200V Chapter 6 Analog input modules
HB97E - SM - Rev. 09/19 6-37
... continue
States, Interrupts, Diagnosis
Diagnostic interrupt parameterizable
Diagnosis functions
- Sum error monitor red SF LED (per channel)
- Diagnostic information read-out possible
Data for selecting a sensor
Voltage
±50mV, ±400mV, ±4V, ±10V
20M
Current
±20mA, 0...20mA, 4...20mA
85
Resistors
0...60, 0...600, 0...3k, 0...6k 20M
Resistance thermometer
Pt100, Pt1000, Ni100, Ni1000, Cu50
20M
Thermocouple
Type J, K, N, R, S, E, T
20M
Maximum input voltage for voltage input
(destruction limit)
25V
Maximum input current for current input
(destruction limit)
30mA
Connection of the sensor
For measuring voltage possible
For measuring current
as 2wire transmitter possible with external power supply
as 4wire transmitter possible
For measuring resistance
with 2conductor connection possible
with 4conductor connection possible
Characteristic linearization
parameterizable yes
for RTD Pt100, Pt1000, Ni100, Ni1000, Cu50
Thermocouple Typ J, K, N, R, S, E, T
Temperature compensation
parameterizable yes
internal temperature compensation possible
external temperature compensation
with comparison point (0°C)
possible
Unit for temperature measurement °C
Parameter data
Input data 8byte (1 Word per channel)
Parameter data 10byte
Diagnostic data 12byte
Dimensions and weight
Dimensions (WxHxD) in mm 25.4x76x88mm
Weight 80g