Technical data

Chapter 6 Analog input modules Manual VIPA System 200V
6-36 HB97E - SM - Rev. 09/19
... continue
Operational limit (only valid to 120W/s)
(in the entire temperature range, with reference to the input range)
Measuring range Tolerance
At voltage input ±50mV ±0.6%
±400mV, ±4V, ±10V ±0.3%
At current input ±20mA ±0.3%
0...20mA ±0.6%
4...20mA ±0.8%
Resistance
0...60
±0.8%
0...600
, 0...3k, 0...6k
±0.4%
Resistance thermometer Pt100, Pt1000 ±0.4%
Ni100, Ni1000 ±1.0%
PTC KTY81-110, 990-1010
1)
PTC KTY81-120, 980-1020
PTC KTY81-121, 980-1000
PTC KTY81-122, 1000-1020
PTC KTY81-150, 950-1050
PTC KTY81-151, 950-1000
PTC KTY81-152, 1000-1050
±1.0%
± Tolerance of the encoder
Cu50 ±1.4%
Thermocouple Type J, K, N, R, S, E, T ±1.5%
Basic error limit (only valid to 120W/s)
(during temperature is 25
°C, referring to input range)
Measuring range Tolerance
Voltage input ±50mV ±0.4%
±400mV, ±4V, ±10V ±0.2%
Current input ±20mA ±0.2%
0...20mA ±0.4%
4...20mA ±0.5%
Resistance
0...60
±0.4%
0...600
, 0...3k, 0...6k
±0.2%
Resistance thermometer Pt100, Pt1000 ±0.2%
Ni100, Ni1000 ±0.5%
PTC KTY81-110, 990-1010
PTC KTY81-120, 980-1020
PTC KTY81-121, 980-1000
PTC KTY81-122, 1000-1020
PTC KTY81-150, 950-1050
PTC KTY81-151, 950-1000
PTC KTY81-152, 1000-1050
±0.5%
± Tolerance of the encoder
Cu50 ±0.7%
Thermocouple Type J, K, N, R, S, E, T ±1.0%
Temperature error
(with reference to the input range)
measuring current
±0.005%/K
±0.015%/K
Linearity error
(with reference to the input range)
±0.02%
Repeatability (in steady state at 25°C
referred to the input range)
±0.05%
Temperature error of internal
compensation
±1.5%
1)
PTC measurement only available starting with firmware version 143 of the module.
continued ...