Technical data
Chapter 6 Analog input modules Manual VIPA System 200V
6-20 HB97E - SM - Rev. 09/19
… continue
No. Function Measurement range / representation Tolerance Conn.
6
)3Ah
Current
±20mA
Siemens S5 format
(two’s complement)
±23.70mA /
23.70mA = max. value before over range (19456)
-20...20mA = nominal range (-16384...16384)
-23.70mA = min. value before under range (-19456)
1)
±0.05%
of final value
(1)
6
)3Bh
Voltage
±10V
Siemens S5 format
(two’s complement)
±11.85V /
12.5V = max. value before over range (20480)
-10...10V = nominal range (-16384...16384)
-12.5V = min. value before under range (-20480)
1)
±0.2%
of final value
(1)
3Dh Resistance measurement
60Ohm 4wire
-
/
60Ω= final value (6000)
1)2)
±0.1%
of final value
(4)
3Eh Resistance measurement
600Ohm 4wire
-
/
600Ω= final value (6000)
1)2)
±0.05%
of final value
(4)
3Fh Resistance measurement
3000Ohm 4wire
-
/
3000Ω = final value (30000)
1)2)
±0.05%
of final value
(4)
57h Voltage 0...50mV
two’s complement
0...50mV
/
59.25mV = max. value before over range (5925)
0...50mV = rated range (0...5000)
1)
±0.1%
of final value
(1)
58h
Voltage
±10V
two’s complement
±11.85V /
11.85V = max. value before over range (11850)
-10...10V = rated range (-10000...10000)
-11.85V = min. value before under range (-11850)
1)
±0.05%
of final value
(1)
59h
Voltage
±4V
two’s complement
±4.74V /
4.74V = max. value before over range (4740)
-4...4V = rated range (-4000...4000)
-4.74V = min. value before under range (-4740)
1)
±0.05%
of final value
(1)
5Ah
Voltage
±400mV
two’s complement
±474mV /
474mV = max. value before over range (4740)
-400...400mV = rated range (-4000...4000)
-474mV = min. value before under range (-4740)
1)
±0.1%
of final value
(1)
5Ch
Current
±20mA
two’s complement
±23.70mA /
23.70mA = max. value before over range (23700)
-20...20mA = rated value (-20000...20000)
-23.70mA = min. value before under range (-23700)
1)
±0.05%
of final value
(1)
5Dh Current 4...20mA
two’s complement
1.185 .. +22.96mA
/
22.96mA = max. value before over range (18960)
4...20mA = rated range (0...16000)
0mA = min. value before under range (-4000)
1)
±0.05%
of final value
(1)
FFh Channel not active (turned off)
1)
measured at an environmental temperature of 25°C, velocity of 15 conversions/s
2)
excluding errors caused by transducer inaccuracies
3)
excluding errors caused by contact resistance and line resistance
4)
the compensation of the neutralization must be implemented externally
5)
the compensation for the neutralization is implemented internally by including the temperature of the front plug. The thermal conductors
have to be connected directly to the front plug, and where necessary these must be extended by means of Thermocouple extension
cables
6)
starting from hardware release 11
Note!
The module is preset to the range "±10V voltage" at S7 format.