Technical data
Manual VIPA System 200V Chapter 6 Analog input modules
HB97E - SM - Rev. 09/19 6-19
… continue
No. Function Measurement range / representation Tolerance Conn.
1Bh Thermocouple type R,
internally compensated
-50
°C .. 1760°C /
in units of 1/10°C, two’s complement
1)2)5)
±5°C
(2)
1Ch Thermocouple type T,
internally compensated
-270
°C .. 400°C /
in units of 1/10°C, two’s complement
1)2)5)
±2°C
(2)
1Dh Thermocouple type S,
internally compensated
-50
°C .. 1760°C /
in units of 1/10°C, two’s complement
1)2)4)
±5°C
(2)
27h Voltage 0...50mV
Siemens S7 format
(two’s complement)
0...50mV
/
59.25mV = max. range before over range (32767)
0...50mV = nominal value (0...27648)
1)
±0.1%
of final value
(1)
28h
Voltage
±10V
Siemens S7 format
(two’s complement)
±11.85V /
11.85V = max. value before over range (32767)
-10...10V = nominal range (-27648...27648)
-11.85V = min. value before under range (-32767)
1)
±0.05%
of final value
(1)
29h
Voltage
±4V
Siemens S7 format
(two’s complement)
±4.74V /
4.74V = max. value before over range (32767)
-4...4V = rated range (-27648...27648)
-4.74V = min. value before under range (-32767)
1)
±0.05%
of final value
(1)
2Ah
Voltage
±400mV
Siemens S7 format
(two’s complement)
±474mV /
474mV = max. value before over range (32767)
-400...400mV = rated range (-27648...27648)
-474mV = min. value before under range (-32767)
1)
±0.1%
of final value
(1)
2Bh
Voltage
±10V
Siemens S5 format
(value and sign)
±11.85V /
12.5V = max. value before over range (20480)
-10...10V = rated range (-16384...16384)
-12.5V = min. value before under range (-20480)
1)
±0.2%
of final value
(1)
2Ch
Current
±20mA
Siemens S7 format
(two’s complement)
±23.70mA /
23.70mA = max. value before over range (32767)
-20...20mA = rated value (-27648...27648)
-23.70mA = min. value before under range (-32767)
1)
±0.05%
of final value
(1)
2Dh Current 4...20mA
Siemens S7 format
(two’s complement)
1.185 .. +22.96mA /
22.96mA = max. value before over range (32767)
4...20mA = rated range (0...27648)
0mA = min. value before under range (-5530)
1)
±0.05%
of final value
(1)
2Eh Current 4...20mA
Siemens S5 format
(two’s complement)
1.185 .. +22.96mA /
22.96mA = max. value before over range (20480)
4...20mA = rated range (0...16384)
0mA = min. value before under range (-4096)
1)
±0.2%
of final value
(1)
2Fh
Current
±20mA
Siemens S5 format
(value and sign)
±23.70mA /
23.70mA = max. value before over range (19456)
-20...20mA = rated value (-16384...16384)
-23.70mA = min. value before under range (-19456)
1)
±0.05%
of final value
(1)
32h Resistance measurement
6000Ohm 4wire
- /
6000
Ω= final value (32767)
1)2)
±0.05%
of final value
(4)
33h Resistance measurement
6000Ohm 4wire
- /
6000
Ω= final value (6000)
1)2)
±0.05%
of final value
(4)
35h Resistance measurement
60Ohm 2wire
- /
60
Ω= final value (6000)
1)2)3)
±0.2%
of final value
(3)
36h Resistance measurement
600Ohm 2wire
- /
600
Ω = final value (6000)
1)2)3)
±0.1%
of final value
(3)
37h Resistance measurement
3000Ohm 2wire
- /
3000
Ω = final value (30000)
1)2)3)
±0.1%
of final value
(3)
38h Resistance measurement
6000Ohm 2wire
- /
6000
Ω = final value (6000)
1)2)3)
±0.1%
of final value
(3)
continued ...