Technical data

Chapter 6 Analog input modules Manual VIPA System 200V
6-18 HB97E - SM - Rev. 09/19
The assignment of a function-no. to a certain channel happens during
parameterization. The function-no. 00h does not influence the function-no.
stored in the permanent parameterization data.
Assigning FFh deactivates the according channel.
No. Function Measurement range / representation Tolerance Conn.
00h Does not affect permanently stored configuration data
01h Pt100 in 2wire mode
-200 .. +850
°C /
in units of 1/10°C, two’s complement
1)2)3)
±1°C
(3)
02h Pt1000 in 2wire mode
-200 .. +500
°C /
in units of 1/10°C, two’s complement
1)2)3)
±1°C
(3)
03h NI100 in 2wire mode
-50 .. +250
°C /
in units of 1/10°C, two’s complement
1)2)3)
±1°C
(3)
04h NI1000 in 2wire mode
-50 .. +250
°C /
in units of 1/10°C, two’s complement
1)2)3)
±1°C
(3)
05h Resistance measurement
60Ohm 2wire
-
/
60= final value (32767)
1)2)3)
±0.2%
of final value
(3)
06h Resistance measurement
600Ohm 2wire
-
/
600 = final value (32767)
1)2)3)
±0.1%
of final value
(3)
07h Resistance measurement
3000Ohm 2wire
-
/
3000 = final value (32767)
1)2)3)
±0.1%
of final value
(3)
08h Resistance measurement
6000Ohm 2wire
- /
6000
= final value (32767)
1)2)3)
±0.1%
of final value
(3)
09h Pt100 via
4wire connection
-200 .. +850
°C /
in units of 1/10°C, two’s complement
1)2)
±0.5°C
(4)
0Ah Pt1000 via
4wire connection
-200 .. +500
°C /
in units of 1/10°C, two’s complement
1)2)
±0.5°C
(4)
0Bh NI100 via
4wire connection
-50 .. +250
°C /
in units of 1/10°C, two’s complement
1)2)
±0.5°C
(4)
0Ch NI1000 via
4wire connection
-50 .. +250
°C /
in units of 1/10°C, two’s complement
1)2)
±0.5°C
(4)
0Dh Resistance measurement
60Ohm 4wire
-
/
60= final value (32767)
1)2)
±0.1%
of final value
(4)
0Eh Resistance measurement
600Ohm 4wire
-
/
600= final value (32767)
1)2)
±0.05%
of final value
(4)
0Fh Resistance measurement
3000Ohm 4wire
-
/
3000 = final value (32767)
1)2)
±0.05%
of final value
(4)
10h Thermocouple type J ,
externally compensated
-210
°C .. 850°C /
in units of 1/10°C, two’s complement
1)2)4)
±1°C
(2)
11h Thermocouple type K,
externally compensated
-270
°C .. 1200°C /
in units of 1/10°C, two’s complement
1)2)4)
±1.5°C
(2)
12h Thermocouple type N,
externally compensated
-200
°C .. 1300°C /
in units of 1/10°C, two’s complement
1)2)4)
±1.5°C
(2)
13h Thermocouple type R,
externally compensated
-50
°C .. 1760°C /
in units of 1/10°C, two’s complement
1)2)4)
±4°C
(2)
14h Thermocouple type T,
externally compensated
-270
°C .. 400°C /
in units of 1/10°C, two’s complement
1)2)4)
±1.5°C
(2)
15h Thermocouple type S,
externally compensated
-50
°C .. 1760°C /
in units of 1/10°C, two’s complement
1)2)4)
±5°C
(2)
18h Thermocouple type J,
internally compensated
-210
°C .. 850°C /
in units of 1/10°C, two’s complement
1)2)5)
±1.5°C
(2)
19h Thermocouple type K,
internally compensated
-270
°C .. 1200°C /
in units of 1/10°C, two’s complement
1)2)5)
±2°C
(2)
1Ah Thermocouple type N,
internally compensated
-200
°C .. 1300°C /
in units of 1/10°C, two’s complement
1)2)5)
±2°C
(2)
continued ...