Technical data

Manual VIPA System 200V Chapter 6 Analog input modules
HB97E - SM - Rev. 09/19 6-15
... continue technical data
Data for selecting a sensor
Input range Input resistance
Current
±20mA
110
4...20mA
110
Maximum input current for current
input (destruction limit)
40mA
Connection of the sensor
for measuring current
as 2wire transmitter possible, with external supply
as 4wire transmitter possible
Permissible environment conditions
Operating temperature 0°C...+60°C
Transport and storage temperature -25°C...+70°C
relative humidity 95% without condensation
Vibration/Shock resistance acc. IEC 68000-2-6/IEC 68000-2-27
EMC resistance
ESD/Burst
acc. IEC 61000-4-2 /
IEC 61000-4-2 /
IEC 61000-4-4 (to level 3)
Project engineering
Input data 8byte (1 Word per channel)
Output data -
Parameter data 10byte
Diagnostics data -
Dimensions and Weight
Dimensions (WxHxD in mm) 25.4x76x88mm
Weight ca. 80g