Technical data

Chapter 4 Digital output modules Manual VIPA System 200V
4-42 HB97E - SM - Rev. 09/19
Wiring diagram Schematic diagram
2
3
4
5
6
7
8
9
10
1
M
internal
V-Bus
DC 30V
A
C 230V
or
+5V
....
Relay output module
Note: When using inductive load please take
a suitable protector
(see installation guidelines).
50 ms
50 ms 50 ms
50 ms
50 ms 50 ms
50 ms
50 ms
Bit set O.0
Bit reset O.0
Relais
open
closed
Note!
Please remember that a relay output that has been set may only be reset
after at least 50ms when the set-signal has been removed.
Electrical data VIPA 222-1HD20
Number of outputs 4 via relay
Nominal load voltage AC 230V or DC 30V
max. output current per channel AC 230V: 16A / DC 30V: 16A
Current consumption
via backplane bus
200mA
Voltage supply DC 5V via backplane bus
Isolation 500Vrms (field voltage to the bus)
Switching rate max. 100Hz
Status indicator -
Programming specifications
Input data -
Output data 1byte
Parameter data -
Diagnostic data -
Dimensions and weight
Dimensions (WxHxD) in mm 25.4x76x88
Weight 80g
Wiring and
schematic
diagram
Signaling diagram
Technical data