Technical data
Chapter 4 Digital output modules Manual VIPA System 200V
4-40 HB97E - SM - Rev. 09/19
Wiring diagram Schematic diagram
2
3
4
5
6
7
8
9
10
1
M
internal
V-Bus
LED
Relay output module
DC 30V
AC 230V
or
+5V
....
Note: When using inductive load please take
a suitable protector
(see installation guidelines).
Maximum load Service life
Electrical data VIPA 222-1HD10
Number of outputs 4 via relay
Nominal load voltage AC 230V or max. DC 30V
max. output current AC 230V: 5A / DC 30V: 5A
Current consumption
via backplane bus
160mA
Voltage supply DC 5V via backplane bus
Isolation 500Vrms (field voltage to the bus)
Switching rate max. 100Hz
Status indicator via LEDs located on the front
Programming specifications
Input data -
Output data 1byte (bit 0 ... bit 3)
Parameter data -
Diagnostic data -
Dimensions and weight
Dimensions (WxHxD) in mm 25.4x76x88
Weight 80g
Wiring and
schematic
diagram
Technical data