Technical data
Chapter 4 Digital output modules Manual VIPA System 200V
4-38 HB97E - SM - Rev. 09/19
Wiring diagram Schematic diagram
2
3
4
5
6
7
8
9
10
1
A
C 230V
or
DC 30V
L
L
M
internal
V-Bus
LED
Relay output module
DC 30V
AC 230V
or
+5V
....
Note: When using inductive load please take
a suitable protector
(see installation guidelines).
Maximum load Service life
Electrical data VIPA 222-1HF00
Number of outputs 8 via relay
Nominal load voltage max. AC 230V or DC 30V
No-load current consumption at L+
(all A.x=off)
-
Current consumption via bus 300mA
Total current with 1 L: max. 8A
with 2 L: max. 16A
max. output current per channel AC 230V: 5A / DC 30V: 5A
Voltage supply DC 5V via backplane bus
Isolation 500Vrms (field voltage to the bus)
Switching rate max. 100Hz
Status indicator via LEDs located on the front
Programming specifications
Input data -
Output data 1byte
Parameter data -
Diagnostic data -
Dimensions and weight
Dimensions (WxHxD) in mm 25.4x76x88
Weight 80g
Wiring and
schematic
diagram
Technical data