Technical data

Chapter 4 Digital output modules Manual VIPA System 200V
4-36 HB97E - SM - Rev. 09/19
... continue
Data for selecting an actuator
Output voltage
- at signal "1"
at maximal current L (-1.3V)
at minimal current L (-0.7V)
Output current
- at signal "1"
Rated value 2A
permitted range for 0°C to 40°C 10mA up to 2A
permitted range for 40°C to 60°C 10mA up to 1.5A
- at signal "0" (leakage current)
100µA
Switch-off delay for resistive load
- "0" to "1" max. 1 AC cycle
- "1" to "0" max. 1 AC cycle
Lamp load max. 460W
Connecting two outputs in parallel
- for redundant triggering of a load not possible
- to increase performance not possible
Short-circuit protection of output yes, electronic
(2A protected against
sustained)