Technical data
Chapter 4 Digital output modules Manual VIPA System 200V
4-34 HB97E - SM - Rev. 09/19
Byte 0 to 9:
Record set 1 contains the 4byte of record set 0 and 6byte module specific
diagnostic data.
The diagnostic bytes have the following assignment:
Record set 1 (Byte 0 to 9):
Byte Bit 7 ... Bit 0 Default
0 ... 3 Content of record set 0 (see page above) -
4 Bit 6 ... 0: Channel type
72h: Digital output
Bit 7: reserved
72h
5 Bit 7 ... 0: Number of diagnostic output bits per channel 08h
6 Bit 7 ... 0: Number of similar channels of a module 02h
7 Bit 0: Channel 0: Channel error
Bit 1: Channel 1: Channel error
Bit 7 ... 2: reserved
00h
8 Bit 0: Channel 0: Parameterization error recognized
Bit 2, 1: reserved
Bit 3: Channel 0: Overload recognized
Bit 5, 4: reserved
Bit 6: Channel 0: Missing load voltage or is failed
Bit 7: Channel 0: Overheat recognized
00h
9 Bit 0: Channel 1: Parameterization error recognized
Bit 2, 1: reserved
Bit 3: Channel 1: Overload recognized
Bit 5, 4: reserved
Bit 6: Channel 1: Missing load voltage or is failed
Bit 7: Channel 1: Overheat recognized
00h