Technical data

Manual VIPA System 200V Chapter 4 Digital output modules
HB97E - SM - Rev. 09/19 4-29
Wiring diagram Schematic diagram
A
C 100
V
... 230
V
1
2
3
4
5
6
7
8
9
10
L
N
N
N
Output module
M
internal
V-Bus
Optocoupler
A
C 100
V
... 230
V
Danger!
The module is not certified for applications in explosive environments
(EX-zone)!
You have to disconnect the module from the main power source before
commencing installation or maintenance work, i.e. before you start to
work the main supply line must be disconnected (disconnect plugs, on
permanent installations the respective fuse has to be turned off)!
Only properly qualified electrical staff is allowed to install, connect
and/or modify electrical equipment!
To provide a sufficient level of ventilation and cooling to the power
supply components whilst maintaining the compact construction it was
not possible to protect the unit from incorrect handling and a proper
level of fire protection. For this reason the required level of fire
protection must be provided by the environment where the power supply
is installed (e.g. installation in a switchboard that satisfies the fire
protection rules and regulations)!
Please adhere to the national rules and regulations of the location
and/or country where the units are installed (installation, safety
precautions, EMC ...).
For each channel the module has an automatic load detection. On each
channel you may connect either an inductive or a capacitive load.
Attention!
Mixing respectively switching over inductive and capacitive loads at one
channel is not allowed. Resistive loads may always be merged.
Wiring and
schematic
diagram
Safety precautions
Automatic load
detection