Safety data sheet

Amperex Technology Limited
新能源科技有限公
3503,Wharf Cable TV Tower, 9 Hoi Shing Road,Tsuen Wan,N.T, HongKong China
香港新界荃湾海盛路 9 号有限电视大楼 35 3 号单元
Tel852-2498-0908 Fax852-2498-1101 http://www.ATLbattery.com
MATERIAL SAFETY DATA SHEET
Issue: 2016-A Doc No.: 2016-A-084
------------------------------------------------------------------------------------------------------------------
Page 4 of 19
6 Neutralized material: prepare 10kg Ca(OH)
2
powder per 500KWh LIB pack or modules,
it was used for neutralized for release electrolyte. Because electrolyte met with water, 8%
HF would be created.
7 Voltage measure. Multimeter. Please physical block the current measure function, the
mistake would lead instrument exploding.
8 People training: (a) turn on fans or portable fans for smoke escape. (b) wear the water
protection sets use water spray fire extinguishers dry by cloths with rubber gloves
insulated by plastic film. (c) neutralized by Ca(OH)
2
or NaOH for released electrolyte.
(d) use multimeter to measure voltage. Take care of the mistake.
5.3 Fire Extinguisher Flow Chart
1 Alarm if you found the smoking or burning.
2 Wear PPE. (Breath mask, face mask. If using water, PPE should include the raincoat,
galoshes, rubber gloves).
3 Turn Off power supply in devices or power supply.
4 Use any fire extinguishers for solid material fire, the recommended sequence was
water or mist water, sand, fire extinguisher blanket, CO
2
, powder.
5 Smoke Escape by turn on fans or open air environment.
6 Dry and neutralize. Drying by fans, Neutralization by Ca(OH)
2
powder if water was
used.
Figure 1 water based fire extinguisher
(Could be used for 36KV electrical fire)
Figure 2 water sprayers to fire extinguisher
(Wear PPE to avoid electrical shock)