Safety data sheet

Amperex Technology Limited
新能源科技有限公
3503,Wharf Cable TV Tower, 9 Hoi Shing Road,Tsuen Wan,N.T, HongKong China
香港新界荃湾海盛路 9 号有限电视大楼 35 3 号单元
Tel852-2498-0908 Fax852-2498-1101 http://www.ATLbattery.com
MATERIAL SAFETY DATA SHEET
Issue: 2016-A Doc No.: 2016-A-084
------------------------------------------------------------------------------------------------------------------
Page 3 of 19
or if irritation persists, seek medical attention.
Eye Contact: Contents of an open battery can cause severe irritation and chemical burns.
Immediately flush eyes thoroughly with water for at least 15 minutes, lifting upper and lower
lids, until no evidence of the chemical remains. Seek medical attention.
Note: Acetylene black and cobalt compounds are listed as possible carcinogens by the
International Agency for Research on Cancer (IARC).
5.Fire Fighting Measures
5.1 Risk Analysis (electrical shock, fire, explode, population)
There was no electrical shock risk for single cell, or battery module which voltage was less
than 50V DC (the safety voltage). But if the pack had the voltage was bigger than 50V DC,
the electrical shock shall be protected.
During the shipment or testing process for LIB Pack or Module, there was danger factors
like drop, crush, broken, metal short circuit, liquid immersion, the factors would lead the risk
like electrical shock, catch fire. If pack was in well sealed box, there was gas explode risk; if
the pack was in big room or fans, there was not explode risk. The released liquid was the
environment population risk.
5.2 Material prepare & people training
1 Water based sprayer fire extinguish: 1 set of 9L or 2 sets of 6L water spray fire
extinguishers per each 500KWh LIB pack or Modules. Or you could use portable
electrical water sprayer or hang type water spray fire extinguisher (photo 1) . The
water based spray fire extinguisher could be used for fire type ABCE = solid (A), flash
point >60 liquid (B), gas (C), <36Kv electrical (E) fire. It was recommended to
prepare water based sprayers in the trucks.
2 Water protection sets: raincoat, galoshes, rubber gloves. Plastic rollers. Rags.
3 PPE: breathing mask, safety glass, face mask, gloves for high temperature.
4 Smoke escape: fans in wall one per 20m or portable fans in rooms. Keep gas exchange
hole in trucks.
5 Gas explode tools: open condition for devices & rooms. Some devices like high or low
temperature ovens must be sealed, there was one copper film with the diameter 200mm &
thickness 8um as the safety vent. The wall should have one fan per 20m, ≥5000m
3
per
hour for flow rate.