Instruction manual
XWEB 3000 – rel.1.7–
1592010600 Pag. 55 / 136
• Insert a new Alarm Level and the attributes
Click into “Name” and insert the word(s) that better represents the alarm eg: ”Severe Alarm”.
• To insert the Receiver
Select the Receiver.
Click the kind of procedure to send the alarm (Fax, E-mail).
Click on “Insert” to add the new item.
• To modify an item
Select the item from the “Selection” roll down menu.
Modify the appropriate fields.
Click on “Modify”.
• To delete an item
Select the user to delete.
Click on “Cancel”.
• To delete all the items of the list
Click on “Cancel All”;
Confirm the operation if necessary. Wait the screen refresh.
• To reset the form
Click on “new”
3.3.4.4 ALARM TYPOLOGY MANAGEMENT
The alarm typology list, designed by the user, groups the common alarm features of the instrument
into an unique definition. For instance all the temperature alarms that are not important can be defined
by a typology named as “Normal Alarm” while the temperature alarms of the frozen food can be
identified by the typology “Severe Alarm”.
The user can assign a typology name for the desired alarm event such as: High temperature, low
temperature, High or pressure, open door, compressor oil, Frozen food, etc…
The user can define the accuracy of the alarm description
Each typology can define the following:
• One of the alarm level previously defined to send the alarm.
• The Delay time that define the minimum duration of alarm. The alarm must be longer to be
computed, otherwise the system will only record the event in the alarm historical list.
• The Accumulation time is a countdown to the alarm sending action. It is useful to send more
than one alarm in a message only. In fact all the alarm belonging to the same typology that
start before accumulation reaches 0, they will be sent in the same message (if the triggered
their delay).
• For each alarm the user can insert the appropriate word(s) that represent(s) the alarm
transmission.
• To inset a new Alarm typology