3.3.6.3 ASSIGN THE CATEGORY TO THE DEVICE “DEVICE CATEGORY SETUP”
Be sure of having selected the right instrument under the “Device” menu.
Depending on the instrument model there are different available categories to define the attributes of the
instrument itself. If you do not find the right one maybe it is not defined or it is not available for that
instrument. By itself XWEB 500, after the recognising procedure, assigns the default categories (if you
checked the box in category window) to the devices connected to the RS 485. To change the category
click inside the field and select the appropriate item.
Click “Modify” now or at the end of the whole configuration.
3.3.6.4 ASSIGN THE ALARM TYPOLOGY
Be sure of having selected the right instrument under the “Device” menu.
ALARM ORIGIN: depending on the instrument model there are different available alarms, if you do not
find the right one it means that it is not available for that instrument.
NAME: each alarm can be assigned with an appropriate label defined by the user, this label is also used
when it is displayed by the system. Click inside the “Name” and modify it.
TIPOLOGY: links alarm type to the proper Alarm typology.
If you do not find the proper action in it, step back to the Alarms definition to insert the new features into
a new alarm typology.
SH (Show): when it is enabled th alarm is showed in main page.
SND (Send): when it is enabled the alarm is sent by XWEB 500.
REC (Recording): when it is enabled the corresponding alarm is logged.
Click “Modify” now or at the end of the whole configuration.
3.3.6.5 DEFINE THE DIGITAL, ANALOGUE INPUTS AND THE STATUS
The middle area is dedicated to the analogue inputs (probe), setpoint, digital inputs, devices status, and
commands assignments.