User manual
1592022700 User manual iCHILL 200CX  Rel. 1.0 22/04/2009 
Pg.96/114
AL 33   
“Antifreeze / low ambient temperature (air / air unit) / low temperature air outlet 
(air/air)” alarm setpoint temperature 
AL31  AL32  °C/°F  Dec/int 
AL 34   
“Antifreeze / low ambient temperature (air / air unit) / low temperature air outlet 
(air/air)” alarm differential temperature 
0.1 
1 
25.0 
45 
°C 
°F 
Dec 
int 
AL 35   
Alarm  delay  for  anti-freeze,  low  ambient  air  temperature  or  low  outlet  air 
temperature 
0  250  Sec   
AL 36   
Maximum number anti-freeze, low ambient air temperature or low  outlet  air 
temperature alarm in chiller 
Always manual reset if AL36 = 0 
Always automatic reset if AL36 = 16 
From automatic to manual if AL36 = 1. .15 
0  16     
AL 37   
Anti-freeze alarm configuration in chiller 
0= when the antifreeze alarm is activated the compressors are switched off; the 
display shows the alarm label, the buzzer and alarm relay are not activated 
1= when the antifreeze alarm is activated the compressors are switched off; the 
display  shows  the  alarm  label,  the  buzzer  and  alarm  relay  are  activated,  the 
antifreeze heathers are acivated 
0  1     
AL 38   
Probe selection for antifreeze alarm in chiller mode 
0= disabled 
1= evaporator inlet temperature 
2= evaporator 1 / 2 outlet temperature 
3= evaporator 1 / 2 outlet temperature and common outlet temperature 
4= external air temperature 
0  4     
AL 39   
Probe selection for condenser antifreeze alarm 
0= disabled 
1= condenser common inlet temperature 
2= condenser 1 / 2 inlet temperature and common inlet temperature 
3= condenser 1 / 2 outlet temperature 
4= condenser 1 / 2 outlet temperature and common outlet temperature 
0  4     
Anti-freeze alarm in Heat pump mode 
AL 40   
Minimum limit of the setpoint in heat pump mode  -50.0 
-58 
AL39 
°C 
°F 
Dec 
int 
AL 41   
Maximum limit of the setpoint in heat pump mode 
AL38 
70.0 
158 
°C 
°F 
Dec 
int 
AL 42   
Anti-freeze alarm setpoint in heat pump 
Setpoint temperature for low anti-freeze alarm, low ambient temperature (air/air), 
low temperature air outlet (air/air) 
AL31  AL32  °C/°F  Dec/int 
AL 43   
Differential of anti freeze alarm in heat pump mode. To reset the anti-freeze, low 
ambient Temperature (air/air), low temperature air outlet (air/air) alarms. 
0.1 
1 
25.0 
45 
°C 
°F 
Dec 
int 
AL 44   
Antifreeze alarm  delay (low outlet temperature for air/air unit)  at  the  stert  up in 
heat pump mode 
0  250  Sec   
AL 45   
Anti-freeze  alarm  delay  for  low  air  ambient  temperature  or  low  outlet  air 
temperature in heat pump normal condition. 
0  250  Sec   
AL 46   
Maximum number of anti-freeze alarm events for low air ambient temperature or 
low outlet air temperature in heat pump. It sets the alarm reset condition: 
Always manual reset AL46 = 0 
Always automatic reset AL46 = 16 
From automatic to manual reset if AL46 = 1..15 
0  16     
AL 47   
Anti-freeze alarm configuration in heat pump 
0= to turn the compressors off when the anti-freeze control probe is  lower than 
AL33 (after the time delay), the display shows the alarm label. 
Buzzer and Alarm relay are not activated. 
1= to turn the compressors off when the anti-freeze control probe is  lower than 
AL33 (after the time delay), the display shows the alarm label. 
Buzzer and Alarm relay are activated. 
0  1     
AL 48   
Probe selection for antifreeze alarm in heat pump mode 
0= disabled 
1= evaporator inlet temperature 
2= evaporator 1 / 2 outlet temperature 
3= evaporator 1 / 2 outlet temperature and common outlet temperature 
4= external air temperature 
0  4     
Compressor high discharge temperature 
AL 49   
Compressor high discharge temperature setpoint  0 
0 
150 
302 
°C 
°F 
Dec / int 
int 
AL 50   
Compressor high discharge temperature differential  0 
0 
25.0 
45 
°C 
°F 
Dec 
int 
AL 51   
Number of compressor high discharge temperature events per hour to determine 
the alarm reset condition: 
Always manual reset if AL51 = 0 
Always automatic reset if AL51 =16 
From automatic to manual if AL51 = 1..15 
0  16     
Generic alarm 1 










