User manual
1592022700 User manual iCHILL 200CX  Rel. 1.0 22/04/2009 
Pg.94/114
dF 18   
Pressure / temperature setpoint to force the ventilation ON during the defrost.  -50.0 
-58 
0.0 
0 
70.0 
158 
50.0 
725 
°C 
°F 
bar 
psi 
Dec 
int 
Dec 
Int 
Forced defrost 
dF 19   
Minimum time delay before a forced defrost  0  250  sec   
dF 20   
Pressure / temperature setpoint for a forced defrost  -50.0 
-58 
0.0 
0 
70.0 
158 
50.0 
725 
°C 
°F 
bar 
psi 
Dec 
int 
Dec 
int 
dF 21   
Forced defrost differential  0.1 
1 
0.0 
0 
25.0 
45 
14.0 
203 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
Defrost operative mode 
dF 22   
Defrost start-up in unit with 2 circuits 
0= Independent 
1= If both have reached the necessary requirements 
2= If one has reached the necessary requirements 
0  2     
dF 23   
End defrost in unit with 2 circuits and common ventilation 
0= Independent 
1= If both have reached the necessary end defrost requirements 
2= If one has reached the necessary end defrost requirements 
0  2     
Start / stop defrost from analog input 
Parameters
description  min  max  udm  resolution 
dF 24   
Start / stop defrost probe 
0= start and stop with condenser temperature / pressure probe 
1=  start  with  evaporator  pressure  probe  /  stop  with  condenser  temperature  / 
pressure probe 
2=  start  with  condenser  temperature  /  pressure    probe  /  stop  with  evaporator 
pressure probe 
3= start and stop with evaporator pressure probe 
0  3     
Supply fan functioning during defrost cycle 
dF 25   
Set point to enable defrost with condenser fan 
-50.0 
-58 
70.0 
158 
°C 
°F 
Dec 
int 
Defrost with condenser fan 
dF 26   
Supply fan status during the defrost cycle 
0= Enabled 
1= Not enabled 
0  1     
Minimum temperature water outlet during defrost 
dF 27   
Probe selection for minimum temperature outlet during defrost  0  6     
dF 28   
Set point for minimum temperature outlet during defrost 
-50.0 
-58 
0.0 
0 
70.0 
158 
50.0 
725 
°C 
°F 
bar 
psi 
Dec 
int 
Dec 
int 
Pr1 
Password   0  999     
Pr2 
Password   0  999     
Pr3 
Password   0  999     
Alarms 
Parameters
Description  min  max  m. u.  Resolution 
Low alarm 
AL 1  
Low pressure alarm delay from analog and digital input  0  250  Sec   
AL 2  
Low pressure alarm delay if the low pressure switch is used for the pump down. 
AL02=  0  low  pressure  alarm  not  enable  during  compressor  switching  off  from 
pump down and if compressor OFF 
AL02≠ 0 low pressure alarm enable after AL02 (starting from compressor switch 
off) time with compressor OFF 
0  250  Sec  10 Sec 
AL 3  
Low pressure alarm setpoint from analogue input  -50.0 
-58 
0.0 
0 
70.0 
158 
50.0 
725 
°C 
°F 
bar 
psi 
Dec 
int 
Dec 
int 
AL 4  
Low pressure alarm differential from analogue input  0.1 
1 
0.0 
0 
25.0 
45 
14.0 
203 
°C 
°F 
bar 
psi 
Dec 
int 
Dec 
Int 
AL 5  
Maximum number of low pressure events from digital/analogue inputs: 
Always manual reset if AL05 = 0 
Always automatic reset if AL05 =16 
From automatic to manual reset if AL05= 1..15 
0  16     
AL 6  
Low temperature/pressure alarm during defrost 
0= Not enabled 
1= Enabled 
0  1     
AL 7  
Low temperature/pressure alarm delay during defrost  0  250  Sec   