User manual

1592022700 User manual iCHILL 200CX Rel. 1.0 22/04/2009
Pg.90/114
US 11
Minimum value of the auxiliary proportional output 1
0 US12 %
US 12
Maximum value of the auxiliary proportional output 1
US11
100 %
US 13
Auxiliary proportional output 1 setpoint
-50.0
-58
0.0
0
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
US 14
Auxiliary proportional output 1 differential
0.1
1
0.0
0
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
Auxiliary proportional output n° 2
US 15
Auxiliary proportional output n° 2 operating mode
0= Not enabled
1= Always available with direct action
2= Available only when the unit is on with direct action
3= Always available with reverse action
4= Available only when the unit is on with reverse action
0 4
US 16
Probe selection for auxiliary proportional output 2
Allows to select which probe value Pb1..Pb10 controls output
1 6
US 17
Minimum value proportional output 2
0 US18 %
US 18
Maximum value proportional output 2
US17
100 %
US 19
Auxiliary setpoint proportional output 2
-50.0
-58
0.0
0
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
US 20
Differenzential proportional output 2
0.1
1
0.0
0
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
Geothermal function
US 21
Geothermal function activation
0= only in chiller
1= only in heat pump
2= chiller and heat pump
0 2
US 22
Temperature to activate geothermal function 0.1
1
0.0
0
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
US 23
Differential to deactivate geothermal function
0.1
1
0.0
0
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
US 24
Time to activate/deactivate geothermal function
0 250 sec
US 25
Probe 1 selection (Pb1..Pb6) for geothermal function 0 6
US 26
Probe 2 selection (Pb1..Pb6) for geothermal function 0 6
US 27
Probes configuration for geothermal function
0= Probe 1 for geothermal function – probe 2 for geothermal function
1= Probe 2 for geothermal function – probe 1 for geothermal function
0 1
US 28
Geothermal function set point -50.0
-58
0
0
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
US 29
Geothermal function differential
0.1
1
0.0
0
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
US 30
Direct / reverse action for geothermal function
0= direct action
1= reverse action
0 1
US 31
Minimum value for geothermal function 0 US32 %
US 32
Maximum value for geothermal function US31
100 %
Pr1
Password 0 999
Pr2
Password 0 999
Pr3
Password 0 999
Condenser fan
Parameters
Description min max M. U. Resolution