CO 82
Time at maximum speed during the switching off of the pump 0 250 sec
Modulating condenser water pump
CO 83
Probe selection (Pb1..Pb6) for modulating condenser water pump in chiller 0 6
CO 84
Probe selection (Pb1..Pb6) for modulating condenser water pump in heat pump 0 6
CO 85
Set point for modulating condenser water pump in chiller -50.0
-58
0
0
70.0
158
50.0
725
°C
Int
Dec
int
CO 86
Proportional band for modulating condenser water pump in chiller 0.1
1
0.1
1
25.0
45
14.0
203
°C
Int
Dec
int
CO 87
Set point for modulating condenser water pump in heat pump -50.0
-58
0
0
70.0
158
50.0
725
°C
Int
Dec
int
CO 88
Proportional band for modulating condenser water pump in heat pump 0.1
1
0.1
1
25.0
45
14.0
203
°C
Int
Dec
int
CO 89
Minimun value of the signal for the modulation of the pump 0 CO90 %
CO 90
Maximun value of the signal for the modulation of the pump CO89 100 %
CO 91
Time at maximum speed when the pump is activated 0 250 sec
CO 92
Value of the signal when the compressor is OFF or when the unit is in STD-BY
or remote OFF
0 100 %
CO 93
Time at maximum speed during the switching off of the pump 0 250 sec
Pr1
Password 0 999
Pr2
Password 0 999
Pr3
Password 0 999
Auxiliary relay
Parameters
Description min max M. U. Resolution
Auxiliary relay of the circuit 1
US 1
Auxiliary relay 1 operating mode
0= Not enabled
1= Always available with direct action
2= Available only when the unit is on with direct action
3= Always available with reverse action
4= Available only when the unit is on with reverse action
0 4
US 2
Probe selection for auxiliary relay 1 control. Allows to select which probe
Pb1..Pb6 controls the relay
1 6
US 3
Auxiliary relay 1 setpoint
-50.0
-58
0.0
0
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
US 4
Auxiliary relay 1 differential
0.1
1
0.0
0
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
Auxiliary relay circuit 2
US 5
Auxiliary relay 2 operating mode
0= Not enabled
1= Always available with direct action
2= Available only when the unit is on with direct action
3= Always available with reverse action
4= Available only when the unit is on with reverse action
0 4
US 6
Probe selection for for auxiliary relay 2 control. Allows to select which probe
value Pb1..Pb6 controls the relay
1 6
US 7
Auxiliary relay 2 setpoint
-50.0
-58
0.0
0
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
US 8
Auxiliary relay 2 differential
0.1
1
0.0
0
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
Auxiliary proportional output n° 1
US 9
Auxiliary proportional output n° 1 operating mode
0= Not enabled
1= Always available with direct action
2= Available only when the unit is on with direct action
3= Always available with reverse action
4= Available only when the unit is on with reverse action
0 4
US 10
Probe selection for auxiliary proportional output 1
Allows to select which probe value Pb1..Pb6 controls output
1 6