User manual
1592022700 User manual iCHILL 200CX  Rel. 1.0 22/04/2009 
Pg.88/114
CO 47   
Minimum ON time of the capacity step after the unloading function start (only for 
capacity compressor) 
0  250  Sec   
Compressor liquid injection 
CO 48   
Setpoint of the solenoid valve (on) of the liquid injection  0 
32 
150 
302 
°C 
°F 
Dec / int 
int 
CO 49   
Setpoint of the solenoid valve (off) of the liquid injection  0.1 
1 
25.0 
45 
°C 
°F 
Dec 
int 
Load management in neutral zone 
CO 50   
Maximum working time in neutral zone without steps insertion  0  250  Min  10 Min 
CO 51   
Maximum working time in neutral zone without steps rotation  0  999  Hr  1Hr 
Pump down to time 
CO 52   
Maximum time for the activation of the pump-down during the switching off 
CO58 = 0 Not enabled 
0  250  Sec   
CO 53   
Maximum time for the activation of the pump-down during the switching on 
CO59 = 0 Not enabled 
0  250  Sec   
Compressor inverter controlled 
CO 54   
Time at maximum speed during compressor start up 
0  250  sec   
CO 55   
Minimum value of the proportional output at compressor start up 
0  100  %   
CO 56   
Minimum interval time of the capacity variation at compressor start up  1  250  sec   
CO 57   
Value under wich starts counting time CO58  0  100  %   
CO 58   
Maximum working time of the compressor with percentage lower than CO57  0  250  Min  10 Min 
CO 59   
Time of forcing the compressor digital scroll to the maximum power 
0  250  sec  10sec 
CO 60   
Maximum working time for compressors rotation 
0  999  Hr  1Hr 
CO 61   
Minimum value of the proportional output digital scroll 0÷10V compressor 1 
0  CO62  %   
CO 62   
Maximum value of the proportional output digital scroll 0÷10V compressor 1 
CO61
100  %   
CO 63   
Minimum value of the proportional output digital scroll 0÷10V compressor 2 
0  CO64  %   
CO 64   
Maximum value of the proportional output digital scroll 0÷10V compressor 2 
CO63
100  %   
CO 65   
Minimum interval time of the capacity variation 
1  250  sec   
Tandem function 
CO 66   
Maximum working time for compressors rotation  0  250  Min   
Solenoid valve water side 
CO 67   
Delay time for compressor activation starting from solenoid valve activation  0  250  Min   
CO 68   
Delay time for solenoid valve deactivation starting from compressor deactivation  0  250  Min   
Unbalanced compressors 
CO 69   
Compressor 1 weight  0  100  %   
CO 70   
Compressor 2 weight  0  100  %   
CO 71   
Maximum numbers of start up per hour 
0= function disabled 
0  60     
Modulating evaporator water pump 
CO 72   
Probe selection (Pb1..Pb6) for modulating evaporator water pump in chiller  0  6     
CO 73   
Probe selection (Pb1..Pb6) for modulating evaporator water pump in heat pump  0  6     
CO 74   
Set point for modulating evaporator water pump in chiller 
-50.0 
-58 
0 
0 
70.0 
158 
50.0 
725 
 °C 
°F 
Bar 
Psi 
Dec 
Int 
Dec 
int 
CO 75   
Proportional band for modulating evaporator water pump in chiller 
0.1 
1 
0.1 
1 
25.0 
45 
14.0 
203 
 °C 
°F 
Bar 
Psi 
Dec 
Int 
Dec 
int 
CO 76   
Set point for modulating evaporator water pump in heat pump 
-50.0 
-58 
0 
0 
70.0 
158 
50.0 
725 
 °C 
°F 
Bar 
Psi 
Dec 
Int 
Dec 
int 
CO 77   
Proportional band for modulating evaporator water pump in heat pump 
0.1 
1 
0.1 
1 
25.0 
45 
14.0 
203 
 °C 
°F 
Bar 
Psi 
Dec 
Int 
Dec 
int 
CO 78   
Minimun value of the signal for the modulation of the pump  0  CO 79  %   
CO 79   
Maximun value of the signal for the modulation of the pump  CO 78
100  %   
CO 80   
Time at maximum speed when the pump is activated  0  250  sec   
CO 81   
Value of the signal when the compressor is OFF or when the unit is in STD-BY 
or remote OFF 
0  100  %   