Partialization (Capacity Control)
CO 6
Functioning (see Capacity Control)
0= On/off steps
1= Continuous insertion of the steps and direct action
2= Continuous insertion of the steps and reverse action
3= Continuous insertion of the steps
0 3
CO 7
Start-up with minimum compressor power / automatic start-unloading valve
0 = Only at the compressor start-up (Minimum power automatic start-unloading
valve off)
1= At the compressor start-up and during the termoregulation (Minimum power /
automatic start-unloading valve off)
2 = Only at the screw compressor start-up (Minimum power automatic start-
unloading valve off)
3= At the compressor start-up and during the termoregulation (Minimum power /
Unloading valve ON with compressor off)
0 3
CO 8
ON time of the intermittent solenoid valve for screw compressor
0= the function is not enabled
0 250 Sec
CO 9
OFF time of the inetrmittent solenoid valve for screw compressor 0 250 Sec
Compressor start-up
CO 10
Compressor start-up selection
0= Direct
1= Part - winding
0 1
CO 11
Part - winding start-up time.
To change the time delay between the activation of two contactors of the two
compressor circuits
0 100 Sec/10 0.1 sec
CO 12
By-pass gas valve start-up time / automatic start-unloading valve (capacity step
control)
0 250 sec
Rotating – Balancing – Compressors Thermoregulation
CO 13
Compressor rotation (See compressor rotation)
0 = Sequential
1 = Compressors rotation based on time running hours
2 = Compressors rotation based on number of starts-up
0 2
CO 14
Circuit balancing (See Circuit balancing)
0= Circuit saturation
1= Circuit balancing
0 1
Evaporator water pump / supply fan
CO 15
Operative mode of the evaporator pump / supply fan
0= Not enabled (evaporator pump or supply fan).
1= ON/OFF: continuous operation type 1
When the unit is running in Chiller or Heat Pump the pump or the supply fan is
running. In std-by or remote OFF mode, the pump is OFF.
2= ON/OFF: on if called by compressor
When a compressor is running, the pump or the supply fan is running.
3= ON/OFF: continuous operation type 2
When the unit is running in Chiller or Heat Pump or in STD-By or in OFF, the
pump or the supply fan is running.
4= Modulation: continuous operation type 1
When the unit is running in Chiller or Heat Pump the pump or the supply fan is
running. In std-by or remote OFF mode, the pump is OFF.
5= Modulation: on if called by compressor
When a compressor is running, the pump or the supply fan is running.
6= Modulation: continuous operation type 2
When the unit is running in Chiller or Heat Pump or in STD-By or in OFF, the
pump or the supply fan is running.
0 6
CO 16
ON compressor delay after water pump / supply fan start-up 1 250 10 sec 10 sec
CO 17
OFF delay evaporator water pump / supply fan after compressor switching OFF.
This delay is also active when the unit is turned in stand-by
0 250 Min
CO 18
Number of running hours for evaporator pump rotation 0 999 10Hr 10Hr
CO 19
Contemporary working time of the pumps during rotation 0 250 Sec
Condenser water pump