CF 56
Firmware Release (this parameter is only in reading)
CF 57
Eeprom parameter map (this parameter is only in reading)
Enabling compressors
CF 58
Enabling compressors
0= chiller and heat pump
1= only chiller
2= only heat pump
0 2
Pr1
Password 0 999
Pr2
Password 0 999
Pr3
Password 0 999
Dynamic Setpoint
Parameters
Description min max M. u. Resolution
Sd 1
Maximum offset for dynamic setpoint function in chiller -30.0
-54
30.0
54
°C
°F
Dec
int
Sd 2
Maximum offset for dynamic setpoint function in heat pump -30.0
-54
30.0
54
°C
°F
Dec
int
Sd 3
Setpoint of outside temperature for dynamic setpoint function in chiller -50.0
-58
70.0
158
°C
°F
Dec
int
Sd 4
Setpoint of outside temperature for dynamic setpoint function in heat pump -50.0
-58
70.0
158
°C
°F
Dec
int
Sd 5
Differential of outside temperature for dynamic setpoint function in chiller -30.0
-54
30.0
54
°C
°F
Dec
int
Sd 6
Differential of outside temperature for dynamic setpoint function in heat pump -30.0
-54
30.0
54
°C
°F
Dec
int
Pr1
Password 0 999
Pr2
Password 0 999
Pr3
Password 0 999
Energy saving
Parameters
Description min max udm Risoluzione
ES 1
Start of the Time band 1 (0÷24) 0 24.00 Hr 10 Min
ES 2
End of the Time Band 1 (0÷24) 0 24.00 Hr 10 Min
ES 3
Start of the Time band 2 (0÷24) 0 24.00 Hr 10 Min
ES 4
End of the Time Band 2 (0÷24) 0 24.00 Hr 10 Min
ES 5
Start of the Time band 3 (0÷24) 0 24.00 Hr 10 Min
ES 6
End of the Time Band 3 (0÷24) 0 24.00 Hr 10 Min
ES 7
Monday: energy saving activated
Automatic unit on-off
0 - 0 7 - 7
ES 8
Tuesday energy saving activated
Automatic unit on-off
0 - 0 7 - 7
ES 9
Wednesday energy saving activated
Automatic unit on-off
0 - 0 7 - 7
ES 10
Thursday energy saving activated
Automatic unit on-off
0 - 0 7 - 7
ES 11
Friday energy saving activated
Automatic unit on-off
0 - 0 7 - 7
ES 12
Saturday energy saving activated
Automatic unit on-off
0 - 0 7 - 7
ES 13
Sunday energy saving activated
Automatic unit on-off
0 - 0 7 - 7
ES 14
Offset for Energy Saving function in chiller mode -30.0
-54
30.0
54
°C
°F
Dec
int
ES 15
Differential for Energy Saving function in chiller 0.1
1
25.0
45
°C
°F
Dec
int
ES 16
Offeset for Energy Saving function in heat pump -30.0
-54
30.0
54
°C
°F
Dec
int
ES 17
Differential for Energy Saving in heat pump 0.1
1
25.0
45
°C
°F
Dec
int
ES 18
Maximum working time of the unit when switched on from keyboard (and the
unit is OFF by Energy saving)
0= Not enabled
0 250 Min 10 Min
Pr1
Password 0 999
Pr2
Password 0 999
Pr3
Password 0 999
Compressors
Parameters
Description min max udm Risoluzione
CO 1
Minimum compressor ON time after the start-up 0 250 10 sec 10 sec
CO 2
Minimum compressor OFF time after the switching off 0 250 10 sec 10 sec
CO 3
ON delay time between two compressors or compressor and valve.
1 250 Sec
CO 4
OFF delay time between two compressors or compressor and valve 0 250 Sec
CO 5