User manual

1592022700 User manual iCHILL 200CX Rel. 1.0 22/04/2009
39.41 ALARM RELAY AND BUZZER
Alarm relay / buzzer outputs
Origin
Alarms still active
Alarms not reset
Reset relay alarm
Whitout alarms
In stand- by or remote ON-OFF if AL59 = 1
Buzzer silencing
By pushing one of the key of the front panel
The alarm relay is enabled only by configurating the corresponding output resource.
39.42 KEYABOARD ALARM
Alarm
code
Keyaboard Alarm description
noL
No data communication between the keyaboard and the regulator.
Atr1
Keyaboard n° 1 set up but not connected to regulator
Atr2
Keyaboard n° 2 set up but not connected to regulator
40 AUTOMATIC TO MANUAL ALARM PROCEDURE
NUMBER OF EVENTS PER HOUR
Each hour counting is divided in 16 intervals, each made of 3600 / 16 = 225 seconds (3 minuts and 45 seconds).
Int
Int
Int
Int
Int
Int
Int
Int
Int
10°Int
11°Int
12°Int
13°Int
14°Int
15°Int
16°Int
After the unit start-up, each interval is marked as “not active”. During the interval counting, for 255seconds, if at least an alarm event
appears, the interval itself is marked “Active”.
Starting from the first interval the instrument calculates the 16 intervals and, at the end, it restats overwriting from the first.
In this way the last hour is always monitored and counted the active intervals. when the number of active intervals reaches the threshold
set with the corresponding parameter the alarm becomes manual.
By setting the threshold (parameter)=0 the alarm is manual from its first activation while if the threshold=16 the alarm is always
automatic (In this case, to change in manual, the threshold should be 17).