39.41  ALARM RELAY AND BUZZER 
Alarm relay / buzzer outputs 
Origin 
Alarms still active 
Alarms not reset 
Reset relay alarm 
Whitout alarms 
In stand- by or remote ON-OFF if AL59 = 1 
Buzzer silencing 
By pushing one of the key of the front panel 
The alarm relay is enabled only by configurating the corresponding output resource. 
39.42  KEYABOARD ALARM 
Alarm 
code 
Keyaboard Alarm description 
noL 
No data communication between the keyaboard and the regulator. 
Atr1 
Keyaboard n° 1 set up but not connected to regulator 
Atr2 
Keyaboard n° 2 set up but not connected to regulator 
40 AUTOMATIC TO MANUAL ALARM PROCEDURE 
NUMBER OF EVENTS PER HOUR 
Each hour counting is divided in 16 intervals, each made of 3600 / 16 = 225 seconds (3 minuts and 45 seconds). 
1°Int
2°Int
3°Int
4°Int
5°Int
6°Int
7°Int
8°Int
9°Int
10°Int
11°Int
12°Int
13°Int
14°Int
15°Int
16°Int
After the unit start-up, each interval is marked as “not active”.  During the interval counting, for 255seconds, if at least an alarm event 
appears, the interval itself is marked “Active”. 
Starting from the first interval the instrument calculates the 16 intervals and, at the end, it restats overwriting from the first. 
In this way the last hour is always monitored and counted the active intervals. when the number of active intervals reaches the threshold 
set with the corresponding parameter the alarm becomes manual. 
By setting the threshold (parameter)=0 the alarm is manual from its first activation while if the threshold=16 the alarm is always 
automatic (In this case, to change in manual, the threshold should be 17). 