air. After the AL44 delay if the anti-freeze probe is still lower than AL42 setpoint for AL45 seconds the unit is locked again with an anti-
freeze alarm.
39.26 B1HP - B2HP HIGH CONDENSING PRESSURE / TEMPERATURE OF THE CIRCUIT
Label on the display b1hP (high pressure analog input of the circuit #1)
b2hP (high pressure analog input of the circuit #2)
Origin
In chiller or heat pump, if the condensing probe is higher than AL09 setpoint.
Reset
If the condensing probe value is lower than AL09 –AL10 (differential)
Restart
Reset procedure in Menu function.
Always manual AL61 = 0
Always automatic AL61 =16
From manual to utomatic if AL61 value is between 1 and 15
Icon
Blinking
Action
Alarm Relay + and buzzer on
Regulation
Condensing fan If FA02=0 the fan is forced at maximum speed for 60 seconds then switched off
If FA02=1 the fan is forced at maximum speed for 60 seconds then regulate according to normal
fan regulation
39.27 B1LP - B2LP LOW PRESSURE SWITCH CIRCUIT #1 OR 2
Label on the display b1LP (low pressure switch circuit #1)
b2LP (low pressure switch circuit #2)
Origin
With the digital input is active
when the low pressure switch input is active (if AL08=1 also in stand-by or remote OFF)
In defrost if AL06=1 when the compressor low pressure switch input is active.
The alarm is not signalled:
during the defrost the alarm is not signalled for AL07 time starting 4-way valve activation
during the regulation the alarm is not signalled for AL01 time strting from compressor
activation
Reset
Digital input not active
Restart
Automatic - Manual after AL05 events per hour (Reset procedure in Menu function)
Icon
Blinking
Action
Alarm Relay + and buzzer on
39.28 B1LP - B2LP LOW EVAPORATING PRESSURE OF THE CIRCUIT (WITH PRESSURE
TRANSDUCERS ONLY)
Label on the display b1lP (low evaporator pressure from analogue input #1)
b2lP (low evaporator pressure from analogue input #2)
Origin
When the evaporator probe value is lower than AL03 setpoint if the unit is:
In chiller or heat pump mode;
Stand-by or remote OFF when AL08 = 1
In defrost when AL06=1
The alarm is not signalled if:
In defrost ,for the time AL07, when the 4-way valve is turned on.
For the time set in AL01 after turning on the compressor.
Reset
When the condensing probe temperature is higher than AL03 + AL04 (differential)
Restart
Automatic– Manual after AL05 events per hour (Reset procedure in Menu function).
Icon
Blinking
Action
Alarm Relay + and buzzer on
ATTENTION When the pressure transducers are configured the low pressure alarms are related only to transducer values.
39.29 B1TF- B2TF CONDENSER FAN OVERLOAD ALARM
Label on the display b1tF (Condenser fan overload alarm of the circuit #1)
b2tF (Condenser fan overload alarm of the circuit #2)
Origin
When the digital input is active
Reset
When the digital input is not active
Restart
Manual (reset from the function menu)
Icon
Blinking
Action
Alarm relay + buzzer ON