38 LOAD MAINTENANCE
PARAMETERS CO24..CO29 are the set of the running hour counters of the loads (compressors and water pumps).
They establish, for each load, the number of running hours limit to display a maintenance message.
If one of these parameters is equal to 0 the maintenance signalling is disabled but the running hours counter remains active.
38.1 LOAD MAINTENANCE RESQUESTS
Label description
C1Mn (maintenance comp. 1), C2Mn (maintenance comp. 2)
AEP1 (maintenance evaporator water pump n° 1)
AEP2 (maintenance evaporator water pump n° 2)
ACP1 (maintenance condenser water pump n° 1)
ACP1 (maintenance condenser water pump n° 2)
Activation
Compressor/pump running hours > counter setpoint for that load
Reset
Running hour reset (Hour label in Menu function)
Restart
Manual
Icon
blinking
Actions
Alarm relay and buzzer activated
REGULATIONS
Actions
Only signalling
Loads
Not modified