37.1.2 Auxiliary relay on reverse action
PBr = NTC probe or transducer selected by the parameters uS02 / uS06
37.2 AUXILIARY FUNCTION ON ANALOG OUTPUTS
The analog outputs OUT1…OUT4 can be configured as auxiliary output.
The function is enabeld if:
• AUX1: parameter uS09≠0 and an analog input configured as “Temperature probe NTC for auxiliary output #1”
• AUX2: parameter uS15≠0 and an analog input configured as “Temperature probe NTC for auxiliary output #2”
uS09 and uS15:
0 = Function disabled
1 = Function alwais enabled on direct action (also if the unit is in STD-BY or remote OFF)
2= Function enabled on direct action only if the unit is ON
3 = Function alwais enabled on reverse action (also if the unit is in STD-BY or remote OFF)
4= Function enabled on reverse action only if the unit is ON
Reverse action:
Direct action: