36 GEOTHERMAL FUNCTION
The function manages an ON/OFF valve (relay) or modulated valve (signal 0..10V) to use, for example, a ground water as cooling
integration.
Configuration:
the function has to be activated by parameter US21
two probes have to be configured by parameters US25 and US26
one relay has to be configured as “valve for geothermal function”
Regulation probes:
if the geothermal function is configured with parameter US27=0 (analog input 1 – analog input 2), the regulation uses the
analog input 1
if the geothermal function is configured with parameter US27=1 (analog input 2 – analog input 1), the regulation uses the
analog input 2
Function activation:
if US27=0: (analog input 1 – analog input 2) > US22 for a minimum time US24
if US27=1: (analog input 2 – analog input 1) > US22 for a minimum time US24
Function deactivation:
if US27=0: (analog input 1 – analog input 2) < US22 –US23 for a minimum time US24
if US27=1: (analog input 2 – analog input 1) < US22 –US23 for a minimum time US24
Relay: geothermal function configured on direct action
Relay: geothermal function configured on reverse action