33 DEFROST CYCLE 
The defrost cycle starts only if all these steps are determined: 
  Heat pump unit 
  DF01≠0 (defrost enabled) 
  The  condenser/evaporator  probe  is  configured (per  circuit)  (if  the evaporator  probe/s  is/are  defined,  the  defrost  cycle  is  always 
controlled by it / them). 
33.1  FORCED DEFROST  
The function is  enabled if  the  parameter dF19<>0. It  allows  to make  a  forced  defrost cycle even if  the  dF09  timeout counting is  not 
expired, when the condensing/evaporating temperature/pressure is lower than dF20 setpoint for the dF19 time counting. 
If during the dF19 time counting the condensing/evaporating temperature/pressure rises above the value dF20+dF21 (set+differential) 
the function is disabled and the dF19 time is reloaded. 
ATTENTION: the forced defrost is not related to the dF09 /dF06 delay times, therefore the forced defrost cycle, if condition are OK, is 
immediately executed. 
33.2  COMBINED DEFROST 
The function is enabled if one of the digital input is configured as NTC temperature for combined defrost of the 1
st
 or 2
nd
 circuit. This 
probe detects  the  external air temperature of the condenser (evaporator in  heat  pump) and determines the  start and the  stop  of  the 
defrost cycle. 
Description of the functioning: 
The count-down to the defrost cycle starts when the temperature/pressure of the probe, configured as condensing/evaporating circuit 1 
or 2 probe, is lower than dF02 parameter. 
After the dF09 counting the instruments checks the temperature probe value (configured as combined defrost circuit 1 or 2) and if it is 
lower  than  dF10  (temperature  setpoint  to  start  the  defrost  of  the  circuit1)  or  dF12  (temperature  setpoint  to  start  the  defrost  of  the 
circuit2) the defrost cycle starts otherwise the unit still runs in heat pump mode. 
When the temperature decreases under the dF10 or dF12 values the defrost immediately start. 
The defrost ends when the NTC combined defrost probe 1 or 2 increases over dF11 (circuit1) or dF13(circuit2). 
If  the  defrost  is  enabled  the  display  allows  to  show  the  external  temperature  on  the  top  display  and  the  labels  dEF1  (circuit1)  or 
dEF2(circuit2) on the bottom display aof the circuit read-out function. 
33.3  MANUAL DEFROST 
The manual defrost key function is enabled if the unit is on with at least one compressor running. 
The defrost start temperature/pressure of the controlled probe must be lower than dF02 setpoint value while if the combined defrost is 
active the detected temperature must be lower than dF10 or dF12. 
At this point by pushing SET + UP for more than 5 seconds the manual defrost starts. 
ATTENTION: the manual defrost is not related to the dF09 /dF06 delay times, therefore the forced defrost cycle, if condition are OK, 
is immediately executed for both circuits. 
33.4  DEFROST START CONDITION WITH TWO CIRCUIT UNIT  
Parameter involved: dF22 
0= Independent 
1= Only if both circuit conditions are satisfied 
2= At least one circuit condition is satisfied 
33.5  START/STOP DEFROST IN A TWO CIRCUITS UNIT WITH ONE CONDENSING FAN CONTROL UNIT 
The table below shows the possible configuration of the parameters dF22 and dF23. 
Parameter  dF23=0  dF23=1  dF23=2 
dF22=0  not possible (ACF1)  not possible (ACF1)  not possible (ACF1) 
dF22=1  not possible (ACF1)  Yes  Yes 
dF22=2  not possible (ACF1)  Yes  not possible (ACF1) 
ATTENTION: 
The configuration error ACF1 is displayed if the parameter value of dF22 and dF23 is not permitted. 
33.6  START/STOP  DEFROST  IN  A  TWO  CIRCUITS UNIT  WITH  TWO  CONDENSING  FAN  CONTROL 
UNIT 
The table below shows the possible configuration of the parameters dF22 and dF23. 
Parameter  dF23=0  dF23=1  dF23=2 