1592022700 User manual iCHILL 200CX  Rel. 1.0 22/04/2009 
Pg.42/114
If the last compressor stops before the pump down pressure switch because of the CO33 time-out (maximum compressor on time after 
turning off the P.D. solenoid valve), the ICHILL calculates the AL28 parameter (maximum number of pump down alarm per hour) and if 
an alarm occurs the display will show the alarm code, the buzzer and the alarm relay will be on. 
If the thermoregulation is stopped via digital input (as  remote off) or from chiller/heat pump keys, during the pump down process the 
chiller or the heat pump led will blink. 
When the next thermoregulation restarts the PD solenoid valve turns on and after 1 seconds, if the pressure probe is higher then CO31, 
the compressors start. 
If the compressors do not restart within the CO33 time the pump-down alarm will signalled and the compressor are stopped. In this case 
if  AL30  =0  the  compressor can  restart  only if the pressure  switch  becomes  active,  or  if  AL30=1  and the number  of  alarms per  hour 
becomes =AL29 only after the manual reset. 
PAR. CO30 = 3  START UNIT WITH PUMP DOWN in CHILLER MODE (No PUMP – DOWN at START-UP) 
In Heat pump mode the Pump down process is inhibited and the solenoid valve works in parallel with the compressor. 
PAR. CO30 = 4  UNIT START/STOP WITH PUMP DOWN in HEAT PUMP 
In Heat pump mode the Pump down process is inhibited and the solenoid valve works in parallel with the compressor. 
23.4  PUMP DOWN ALARM DURING COMPRESSORS START- UP 
ACTIVATION 
If  within  the  CO33 delay time (Maximum  pump  down restart  time)  the  compressor/s do  not  restart because  of  the  low pressure, the 
instrument will signal B1PL (pump down alarm at the start-up of the circuit 1) or the label B2PL (pump down alarm at the start-up of the 
circuit 2). With active alarm the restart procedure is disabled. The alarms can be: 
•  with Automatic Reset that is not logged, the buzzer and alarm relay are not activated. 
•  with Manual Reset that is logged, the buzzer and alarm relay are activated. 
The parameter AL29 determines the number of pump down alarm events to turn from automatic to manual reset 
The Reset is always manual if AL29 = 0 
The Reset is always automatic if AL29 = 16 
The reset becomes manual after AL29 = 1 ..15 events and the configuration of Par. AL30. 
Par. AL30 defines if the reset of the AL29 alarm events can be forced from manual to automatic. In this case the alarm events, after 
reaching AL29, is automatically reset but it is logged while the buzzer and the alarm relay are on. 
In this way, in case of particularly critical condition, the unit restarts working without the help of the maintenance personnel. 
RESET 
•  The Automatic Reset is activated when the next compressor thermoregulation is requested, in this case the pressure condition of 
the pump down must be satisfied. 
•  The Manual Reset needs to enter the function Menu under the AlrM label. After the reset the next thermoregulation restarts if the 
pump down pressure is in normal condition. 
ATTENTION 
If the pump down function is enabled, during the unit start-up from digital input as pump down pressure switch and also from 
analogue input as low pressure transducer, the compressor will restart only if both the inputs are satisfied. 
23.5  PUMP DOWN ALARM DURING COMPRESSORS SWITCHING OFF 
ACTIVATION 
If within the time delay CO33 (maximum pump down duration in off) the low pressure switch or the pump down pressure switch is not 
active  or  the  pump  down  setpoint  is  not  reached,  the  last  compressor  is  switched  off.  In  this  case after  this  timeout  the  instrument 
signals the B1PH or 2 alarms, in both cases when active the compressor is stopped. 
The alarm can be: 
•  with Automatic Reset that is not logged, the buzzer and alarm relay are not activated. 
•  with Manual Reset that is logged, the buzzer and alarm relay are activated. 
The Parameter AL28 determines the number of pump down alarm events to turn from automatic to manual reset 
The Reset is always manual if AL28 = 0. 
The Reset is always automatic if AL28 = 16. 
The reset becomes manual after AL28 = 1 ..15. 
RESET 
•  The Automatic Reset is activated when the next compressor thermoregulation is requested, in this case the pressure condition of 
the pump down must be satisfied. 
•  The Manual Reset needs to enter the function Menu under the AlrM label. After the reset the next thermoregulation restarts if the 
pump down pressure is in normal condition. 
ATTENTION 
If the pump down function is enabled, during the unit start-up from digital input as pump down pressure switch and also from 
analogue input as low pressure transducer, the compressor will restart only if both the inputs are satisfied. 
23.6  PUMP DOWN BY DELAY TIME 