Part Winding 1 of the compressor 2 
34.  Part Winding 2 of the compressor 2 
35.  Capacity step valve 1 compressor 2 
36.  By-pass gas valve compressor 2 start 
9.5  ANALOG OUTPUT CONFIGURATION 0 ÷ 10 VOLT (OUT1 E OUT2) 
Parametri: 
CF43 = Analog output OUT1 configuration 
CF44 = Analog output OUT2 configuration 
0  = output disabled 
1  = 0..10V output for compressor 1 inverter controlled 
2  = 0..10V output for compressor 2 inverter controlled 
3  = 0..10V output for auxiliary output 1 
4  = 0..10V output for auxiliary output 2 
5  = 0..10V output for geothermal function 
6  = 0..10V output for condenser fan circuit 1 
7  = 0..10V output for condenser fan circuit 2 
8  = 0..10V output for modulating evaporator pump 
9  = 0..10V output for modulating condenser pump 
o1..c26 = ON / OFF output for external relay management (same meaning of relays configuration) 
9.6  CONFIGURAZIONE N°  2 USCITE  ANALOGICHE  0  ÷ 10  VOLT  /  TAGLIO  DI  FASE  (OUT3  E 
OUT4) 
Parametri: 
CF45 = Configurazione uscita analogica n° 3 
CF46 = Configurazione uscita analogica n° 4 
0  = output disabled 
1  = 0..10V output for compressor 1 inverter controlled 
2  = 0..10V output for compressor 2 inverter controlled 
3  = 0..10V output for auxiliary output 1 
4  = 0..10V output for auxiliary output 2 
5  = 0..10V output for geothermal function 
6  = 0..10V output for condenser fan circuit 1 
7  = 0..10V output for condenser fan circuit 2 
8  = PWM output for condenser fan circuit 1 
9  = PWM output for condenser fan circuit 2 
o1..c26 = OFF output for external relay management (same meaning of relays configuration) 