User manual

1592022700 User manual iCHILL 200CX Rel. 1.0 22/04/2009
Pg.20/114
Part Winding 1 of the compressor 2
34. Part Winding 2 of the compressor 2
35. Capacity step valve 1 compressor 2
36. By-pass gas valve compressor 2 start
9.5 ANALOG OUTPUT CONFIGURATION 0 ÷ 10 VOLT (OUT1 E OUT2)
Parametri:
CF43 = Analog output OUT1 configuration
CF44 = Analog output OUT2 configuration
0 = output disabled
1 = 0..10V output for compressor 1 inverter controlled
2 = 0..10V output for compressor 2 inverter controlled
3 = 0..10V output for auxiliary output 1
4 = 0..10V output for auxiliary output 2
5 = 0..10V output for geothermal function
6 = 0..10V output for condenser fan circuit 1
7 = 0..10V output for condenser fan circuit 2
8 = 0..10V output for modulating evaporator pump
9 = 0..10V output for modulating condenser pump
o1..c26 = ON / OFF output for external relay management (same meaning of relays configuration)
9.6 CONFIGURAZIONE 2 USCITE ANALOGICHE 0 ÷ 10 VOLT / TAGLIO DI FASE (OUT3 E
OUT4)
Parametri:
CF45 = Configurazione uscita analogica n° 3
CF46 = Configurazione uscita analogica n° 4
0 = output disabled
1 = 0..10V output for compressor 1 inverter controlled
2 = 0..10V output for compressor 2 inverter controlled
3 = 0..10V output for auxiliary output 1
4 = 0..10V output for auxiliary output 2
5 = 0..10V output for geothermal function
6 = 0..10V output for condenser fan circuit 1
7 = 0..10V output for condenser fan circuit 2
8 = PWM output for condenser fan circuit 1
9 = PWM output for condenser fan circuit 2
o1..c26 = OFF output for external relay management (same meaning of relays configuration)