User manual
1592022700 User manual iCHILL 200CX  Rel. 1.0 22/04/2009 
PARAMETER 
VALUE 
DESCRIPTION 
CORRESPONDING 
LABEL 
0 
No display read out  
No label 
1 
NTC temperature probe of the evaporator water inlet 
Ein 
2 
NTC temperature probe of the evaporator water outlet 1 and 2 
Out1 circuit 1 
Out2 circuit 2 
3 
NTC temperature probe of the common evaporator water outlet 
Eout 
4 
NTC temperature probe of the condenser water inlet 
CIn1 circuit 1 
CIn2 circuit 2 
5 
NTC temperature probe of the common condenser water inlet 
Cin 
6 
NTC temperature probe of the condenser water outlet 
Cou1 circuit 1 
Cou2 circuit 2 
7 
NTC temperature probe of the common condenser water outlet 
Cout 
8 
NTC temperature probe of the dynamic setpoint 
Et 
9 
NTC temperature probe of the remote terminal 1 
trE1 
10 
NTC temperature probe of the remote terminal 2 
trE2 
11 
NTC temperature probe for the combined defrost 
dEF1 circuit 1 
dEF2 circuit 2 
12 
NTC temperature probe of the condenser 
Cdt1 circuit 1 
Cdt2 circuit 2 
13 
Set  point  (set  point  chiller  or  set point  heat  pump  when the  controller  is  ON;  “OFF” 
when the controller is OFF or STD-BY) 
14 
Differential of regulation in chiller or heat pump 
15 
Machine status (OFF / OnC=ON chiller / OnH=ON heat pump) 
16 
Pressure probe of the condenser 
CdP1 circuit 1 
CdP2 circuit 2 
17 
Pressure probe of the evaporator 
LP1 circuit 1 
LP2 circuit 2 
18 
Clock 
4.2  FORCED READ - OUT OF THE TOP AND BOTTOM DISPLAY 
To force the display read-out: 
1.  Set the dP03 parameter different to 0  
2.  Select the value range 1..3 
These configurations allow to show together two temperatures or two pressures of the same circuit in order to have an easier reading of 
the measurements: 
Par. dP03 = 1 
Top display: for both the circuits 1,2: 
•  Evaporator water inlet, with the Ein label. 
Bottom display: circuit 1: 
•  Evaporator 1 water outlet, with the label OuT1 
Bottom display: circuit 2: 
•  Evaporator 2 water outlet, with the label OuT2. 
Par. dP03 = 2 
Top display of the circuit 1: 
•  Condenser 1 water inlet temperature with the label CIn1 
Bottom display of the circuit 1 
•  Condenser 1water outlet with the label COu1. 
Top display of the circuit 2: 
Condenser 2 water inlet temperature with the label Cin2 
Bottom display of the circuit 2 
•  Condenser 2water outlet with the label Cou2. 
Par. dP03 = 3 
Top display of the circuit 1: 