User manual
1592022700 User manual iCHILL 200CX Rel. 1.0 22/04/2009
Pg.10/114
Main display (upper display)
Parameters dP01 (IC200CX), dP05 (remote keyboard n°1), dP07 (remote keyboard n°2)
PARAMETER
VALUE
DESCRIPTION
CORRESPONDING
LABEL
0
No display read out
No label
1
NTC temperature probe of the evaporator water inlet
Ein
2
NTC temperature probe of the evaporator water outlet 1 and 2
Out1 circuit 1
Out2 circuit 2
3
NTC temperature probe of the common evaporator water outlet
Eout
4
NTC temperature probe of the condenser water inlet
CIn1 circuit 1
CIn2 circuit 2
5
NTC temperature probe of the common condenser water inlet
Cin
6
NTC temperature probe of the condenser water outlet
Cou1 circuit 1
Cou2 circuit 2
7
NTC temperature probe of the common condenser water outlet
Cout
8
NTC temperature probe of the dynamic setpoint
Et
9
NTC temperature probe of the remote terminal 1
trE1
10
NTC temperature probe of the remote terminal 2
trE2
11
NTC temperature probe for the combined defrost
dEF1 circuit 1
dEF2 circuit 2
12
NTC temperature probe of the condenser
Cdt1 circuit 1
Cdt2 circuit 2
13
Set point (set point chiller or set point heat pump when the controller is ON; “OFF”
when the controller is OFF or STD-BY)
14
Differential of regulation in chiller or heat pump
15
Machine status (OFF / OnC=ON chiller / OnH=ON heat pump)
Secondary display (lower display)
Parameters dP02 (IC200CX), dP06 (remote keyboard n°1), dP08 (remote keyboard n°2)