49 TECHNICAL DATA 
Housing: self extinguishing ABS. 
Case: frontal 32x74 mm; depth 60mm 
Mounting: panel mounting in a 29x71mm panel cut-out 
Frontal protection: IP65 
Display: 
Top Display 4 digits with d.p. 
 Bottom Display 4 digits with d.p. 
Power supply: 
12Vac -10%÷+15% or 
 24 Vac/dc ±10% 50/60 Hz 
Power absorption: 10VA max. 
Analog Inputs: 4 configurable (NTC/PTC/dig. input) + 2 configurable (NTC/PTC/4÷20ma/0÷5Volt/dig. input) 
Digital inputs: # 11 (free voltage) 
Relay outputs: IC206CX: 6 SPDT 5(2) A, 250Vac, IC208CX: 8 SPDT 5(2) A, 250Vac 
Max. current on common line: 10A 
Data storing: on the non-volatile memory (EEPROM). 
Operating temperature: 0÷55 °C. 
Storage temperature: -30÷85 °C. 
Relative humidity: 20÷85% (no condensing) 
Measuring range: - 50÷110 °C (- 58 ÷ 230 °F) NTC / -50.0÷150 °C (-58÷302 °F) PTC or 0÷ 50 bar (0÷725 
psi) 
Resolution: 0,1 °C or 1 °F 
Accuracy of the controller at 25°C: ±0,7 °C ±1 digit 