47 ELECTRICAL CONNECTIONS
The instrument is provided with:
• 2 removable terminal blocks MOLEX MICROFIT 14 and 18 ways for power supplay / digital and analogue inputs and modulating
outputs
• 1 removable terminal blocks AMP 12 ways for the relay outputs
• 5 ways connector for TTL RS485 interface outputs.
Wire size:
• signal cable AWG 24
• power supply cable AWG 22
• relay output AWG 17
General notes:
• Check the connecitons and the line voltage before turning on the power supply.
• Keep low voltage cables, such as analogue/digital inputs/outputs and probes, away from power cables and terminals.
• Respect the maximum load current of each relay output, in case of power loads use filtered contactors.
48 ACCESSORIES
48.1 MONOPHASE FAN CONTROL: 230VAC AND CUT PHASE CONTROL
Models XV05PK XV10PK XV22PK
Power 500W 1000W 2200W
Ampere 2A 4A 9.5A
Power supply
230Vac Input
0 - 230Vac output
-10 - 65°C Operating temperature
Naylon supports
D
15mm
Height
Model
XV05PK XV10PK XW22PK
Y
25mm 42mm 64mm
Connections
A 1(+), 2(-) PWM input control
B 3(+), 4(-) PWM output repetition signal
F
Phase
N
Neutral
5 - 6
Fan output
Terminals 3 and 4 allows to connect another board in parallel to control two separate fans with the same input control.
Terminals 1 / 2 / 3 / 4 are for screw for a 2.5mm wire
Terminals 5 / 6 / F / N are 6,3mm faston