User manual

1592022700 User manual iCHILL 200CX Rel. 1.0 22/04/2009
Pg.100/114
44.2 HARDWARE RESOURCES FOR 208CX MODELS
8 digital outputs (relays) MAX current on the relay contacts relè 5(2)A 250V - MAX common current 10A 250V
11 digital inputs (free of voltage)
6 analogue inputs:
4 NTC / PTC probes
2 NTC / PTC / pressure transducer 4÷20 mA / pressure transducer ratio-metric 0÷ 5.0 Volt
4 modulating outputs:
2 configurable 0 ÷ 10 Volt
2 configurable 0 ÷ 10.0 Volt or cut of phase (for modulating condenser fan)
1 output to connect a remote keyboard (max 2 remote keyboards)
1 TTL output for “Hot Key 64” or for XJ485CX (interface module for monitoring system)
44.3 ANALOG INPUTS NTC PTC PROBES
PbC = common terminal
Pb1…Pb6 = probe inputs