1592022700 User manual iCHILL 200CX Rel. 1.0 22/04/2009
43 BLACK-OUT
After the black-out is restored:
1. The instrument restores the same operating mode lost after the supply failure.
2. If active, the defrost is aborted.
3. All the timers and time parameters are reloaded.
4. The manual alarm is not reset.
44 WIRING CONNECTIONS
44.1 HARDWARE RESOURCES FOR IC206CX MODEL
6 digital outputs (relays) MAX current on the relay contacts relè 5(2)A 250V - MAX common current 10A 250V
11 digital inputs (free of voltage)
6 analogue inputs:
4 NTC / PTC probes
2 NTC / PTC / pressure transducer 4÷20 mA / pressure transducer ratio-metric 0÷ 5.0 Volt
4 modulating outputs:
2 configurable 0 ÷ 10 Volt
2 configurable 0 ÷ 10.0 Volt or cut of phase (for modulating condenser fan)
1 output to connect a remote keyboard (max 2 remote keyboards)
1 TTL output for “Hot Key 64” or for XJ485CX (interface module for monitoring system)