User manual
1592022700 User manual iCHILL 200CX Rel. 1.0 22/04/2009
AL 52
Maximum number of generic alarm events (each event stop the regulation)
before turning the alarm from automatic to manual:
Always manual AL52 = 0
Always automatic AL52 =16
From manual to utomatic if AL52 value is between 1 and 15
0 16
AL 53
Generic alarm delay time after the digital input activation 0 250 Sec
AL 54
Generic alarm delay time after the digital input is not activate 0 250 10 sec 10 sec
Generic alarm / signal 2
AL 55
Functioning generic alarm n° 2
0= only signal always automatic reset
1= the alarm block the unit reset depends on the value of parameter AL56
0 1
AL 56
Maximum number of generic alarm events before turning the alarm from
automatic to manual:
Always manual AL56 = 0
Always automatic AL56 =16
From manual to utomatic if AL56 value is between 1 and 15
0 16
AL 57
Generic alarm delay time after the digital input activation 0 250 Sec
AL 58
Generic alarm delay time after the digital input is not activate 0 250 Sec 10 sec
Alarm relay
AL 59
Enable alarm relay with unit in off or stand – by:
0= Alarm output not enabled
1= Alarm output enabled
0 1
Password reset: Alarm log – Compressor overload
AL 60
Password value to reset the alarm log or the compressor overload alarm. 0 999
Reset High pressure / temperature alarm
AL 61
Maximum number of high pressure / temperature alarm events before turning the
alarm from automatic to manual:
Always manual AL61 = 0
Always automatic AL61 =16
From manual to utomatic if AL61 value is between 1 and 15
0 16
High water evaporator inlet temperature
AL 62
Maximum number of high water temperature alarm events
Always manual reset if AL62 = 0
Always automatic reset if AL62 =16
From automatic to manual reset if AL62 =1..15
1 16
AL 63
High water temperature alarm delay time starting from ON compressor 0 250 Sec 10 sec
AL 64
High water evaporator inlet temperature set point -50.0
-58
70.0
158
°C
°F
Dec
int
AL 65
High water evaporator inlet temperature differential 0.1
1
25.0
45
°C
°F
Dec
int
AL 66
Probe selection for high water evaporator inlet temperature
Allows to select which probe (Pb1..Pb6) the function uses
1 6
Low water evaporator inlet temperature
AL 67
Maximum number of low water temperature alarm events
Always manual reset if AL67 = 0
Always automatic reset if AL67 =16
From automatic to manual reset if AL67 =1..15
1 16
AL 68
Low water temperature alarm delay time starting from ON compressor 0 250 Sec 10 sec
AL 69
Low water evaporator inlet temperature set point -50.0
-58
70.0
158
°C
°F
Dec
int
AL 70
Low water evaporator inlet temperature differential 0.1
1
25.0
45
°C
°F
Dec
int
AL 71
Probe selection for low water evaporator inlet temperature
Allows to select which probe value NTC/PTC Pb1..Pb6
1 6
Inlet / outlet water tempearture differential alarm
AL 72
Inlet / outlet water tempearture differential alarm enable
0= disabled
1= only in chiller mode
2= only in heat pump mode
3= in chiller and heat pump mode
0 3
AL 73
Maximum number of Inlet / outlet water tempearture differential alarm
Always manual reset if AL73 = 0
Always automatic reset if AL73 =16
From automatic to manual reset if AL73 =1..15
1 16
AL 74
Inlet / outlet water tempearture differential alarm delay time starting from ON
compressor
0 250 Sec 10 sec
AL 75
Inlet / outlet water tempearture differential alarm set point in chiller mode -50.0
-58
70.0
158
°C
°F
Dec
int
AL 76
Inlet / outlet water tempearture differential alarm differential in chiller mode 0.1
1
25.0
45
°C
°F
Dec
int
AL 77
Inlet / outlet water tempearture differential alarm set point in heat pump mode -50.0
-58
70.0
158
°C
°F
Dec
int
AL 78
Inlet / outlet water tempearture differential alarm differential in heat pump mode 0.1
1
25.0
45
°C
°F
Dec
int