Technical data
1592022750 Quick reference guide IC 200CX  Rel. 1.1 25/05/2009 
•  signal cable AWG 24 
•  power supply cable AWG 22 
•  relay output AWG 17 
General notes: 
•  Check the connecitons and the line voltage before turning on the power supply. 
•  Keep low voltage cables, such as analogue/digital inputs/outputs and probes, away from power 
cables and terminals. 
•  Respect  the  maximum  load  current  of  each  relay  output,  in  case  of  power  loads  use  filtered 
contactors. 
18 TECHNICAL DATA 
Housing: self extinguishing ABS. 
Case: frontal 32x74 mm; depth 60mm 
Mounting: panel mounting in a 29x71mm panel cut-out 
Frontal protection: IP65 
Display: 
Top Display 4 digits with d.p. 
 Bottom Display 4 digits with d.p. 
Power supply: 
12Vac -10%÷+15% or 
 24 Vac/dc ±10% 50/60 Hz 
Power absorption: 10VA max. 
Analog Inputs: 4 configurable (NTC/PTC/dig. input) + 2 configurable (NTC/PTC/4÷20ma/0÷5Volt/dig. 
input) 
Digital inputs: # 11 (free voltage) 
Relay outputs: IC206CX: 6 SPDT 5(2) A, 250Vac, IC208CX: 8 SPDT 5(2) A, 250Vac 
Max. current on common line: 10A 
Data storing: on the non-volatile memory (EEPROM). 
Operating temperature: 0÷55 °C. 
Storage temperature: -30÷85 °C. 
Relative humidity: 20÷85% (no condensing) 
Measuring range: - 50÷110 °C (- 58 ÷ 230 °F) NTC /  -50.0÷150 °C (-58÷302 °F) PTC or 0÷ 50 bar 
(0÷725 psi) 
Resolution: 0,1 °C or 1 °F 
Accuracy of the controller at 25°C: ±0,7 °C ±1 digit 
Dixell S.p.A. Z.I. Via dell’Industria, 27 
32010 Pieve d’Alpago (BL) ITALY 
tel. +39 - 0437 - 98 33  -  fax +39 - 0437 - 
98 93 13 
E-mail:dixell@dixell.com 
http://www.dixell.com 