Technical data
1592022750 Quick reference guide IC 200CX  Rel. 1.1 25/05/2009 
AL 67
Maximum number of low water temperature alarm events 
Always manual reset if AL67 = 0 
Always automatic reset if AL67 =16 
From automatic to manual reset if AL67 =1..15 
1  16     
AL 68
Low water temperature alarm delay time starting from ON compressor
0  250  Sec  10 sec 
AL 69
Low water evaporator inlet temperature set point  -50.0 
-58 
70.0 
158 
°C 
°F 
Dec 
int 
AL 70
Low water evaporator inlet temperature differential  0.1 
1 
25.0 
45 
°C 
°F 
Dec 
int 
AL 71
Probe selection for low water evaporator inlet temperature 
Allows to select which probe value NTC/PTC Pb1..Pb6 
1  6     
Inlet / outlet water tempearture differential alarm 
AL 72
Inlet / outlet water tempearture differential alarm enable 
0= disabled 
1= only in chiller mode 
2= only in heat pump mode 
3= in chiller and heat pump mode 
0  3     
AL 73
Maximum number of Inlet / outlet water tempearture differential alarm 
Always manual reset if AL73 = 0 
Always automatic reset if AL73 =16 
From automatic to manual reset if AL73 =1..15 
1  16     
AL 74
Inlet  /  outlet  water  tempearture  differential  alarm  delay  time  starting 
from ON compressor 
0  250  Sec  10 sec 
AL 75
Inlet  /  outlet  water  tempearture  differential  alarm  set  point  in  chiller 
mode 
-50.0 
-58 
70.0 
158 
°C 
°F 
Dec 
int 
AL 76
Inlet /  outlet  water tempearture differential alarm  differential in chiller 
mode 
0.1 
1 
25.0 
45 
°C 
°F 
Dec 
int 
AL 77
Inlet /  outlet water  tempearture differential alarm  set point in  heat 
pump mode 
-50.0 
-58 
70.0 
158 
°C 
°F 
Dec 
int 
AL 78
Inlet  /  outlet  water  tempearture  differential  alarm  differential  in  heat 
pump mode 
0.1 
1 
25.0 
45 
°C 
°F 
Dec 
int 
AL 79
Probe 1 selection for Inlet / outlet water tempearture differential alarm 
Allows to select which probe value NTC/PTC Pb1..Pb6 
1  6     
AL 80
Probe 2 selection for Inlet / outlet water tempearture differential alarm 
Allows to select which probe value NTC/PTC Pb1..Pb6 
1  6     
Pr1 
Password  0  999     
Pr2 
Password  0  999     
Pr3 
Password  0  999     
14 BLACK-OUT 
After the black-out is restored: 
1.  The instrument restores the same operating mode lost after the supply failure. 
2.  If active, the defrost is aborted. 
3.  All the timers and time parameters are reloaded. 
4.  The manual alarm is not reset. 