Technical data
1592022750 Quick reference guide IC 200CX  Rel. 1.1 25/05/2009 
AL 51
Number of compressor high discharge temperature events per hour to 
determine the alarm reset condition: 
Always manual reset if AL51 = 0 
Always automatic reset if AL51 =16 
From automatic to manual if AL51 = 1..15 
0  16     
Generic alarm 1 
AL 52
Maximum  number  of  generic  alarm  events  (each  event  stop  the 
regulation) before turning the alarm from automatic to manual: 
Always manual AL52 = 0 
Always automatic AL52 =16 
From manual to utomatic if AL52 value is between 1 and 15 
0  16     
AL 53
Generic alarm delay time after the digital input activation  0  250  Sec   
AL 54
Generic alarm delay time after the digital input is not activate  0  250  10 sec  10 sec 
Generic alarm / signal 2 
AL 55
Functioning generic alarm n° 2 
0= only signal always automatic reset 
1= the alarm block the unit reset depends on the value of parameter 
AL56 
0  1     
AL 56
Maximum  number  of  generic  alarm  events  before  turning  the  alarm 
from automatic to manual: 
Always manual AL56 = 0 
Always automatic AL56 =16 
From manual to utomatic if AL56 value is between 1 and 15 
0  16     
AL 57
Generic alarm delay time after the digital input activation  0  250  Sec   
AL 58
Generic alarm delay time after the digital input is not activate  0  250  Sec  10 sec 
Alarm relay 
AL 59
Enable alarm relay with unit in off or stand – by: 
0= Alarm output not enabled 
1= Alarm output enabled 
0  1     
Password reset: Alarm log – Compressor overload 
AL 60
Password  value  to  reset  the  alarm  log  or  the  compressor  overload 
alarm. 
0  999     
Reset High pressure / temperature alarm 
AL 61
Maximum number of high pressure / temperature alarm events before 
turning the alarm from automatic to manual: 
Always manual AL61 = 0 
Always automatic AL61 =16 
From manual to utomatic if AL61 value is between 1 and 15 
0  16     
High water evaporator inlet temperature 
AL 62
Maximum number of high water temperature alarm events 
Always manual reset if AL62 = 0 
Always automatic reset if AL62 =16 
From automatic to manual reset if AL62 =1..15 
1  16     
AL 63
High  water  temperature  alarm  delay  time  starting  from  ON 
compressor 
0  250  Sec  10 sec 
AL 64
High water evaporator inlet temperature set point  -50.0 
-58 
70.0 
158 
°C 
°F 
Dec 
int 
AL 65
High water evaporator inlet temperature differential  0.1 
1 
25.0 
45 
°C 
°F 
Dec 
int 
AL 66
Probe selection for high water evaporator inlet temperature 
Allows to select which probe (Pb1..Pb6) the function uses 
1  6     
Low water evaporator inlet temperature 