Technical data
1592022750 Quick reference guide IC 200CX  Rel. 1.1 25/05/2009 
AL 38
Probe selection for antifreeze alarm in chiller mode 
0= disabled 
1= evaporator inlet temperature 
2= evaporator 1 / 2 outlet temperature 
3=  evaporator  1  /  2  outlet  temperature  and  common  outlet 
temperature 
4= external air temperature 
0  4     
AL 39
Probe selection for condenser antifreeze alarm 
0= disabled 
1= condenser common inlet temperature 
2= condenser 1 / 2 inlet temperature and common inlet temperature 
3= condenser 1 / 2 outlet temperature 
4=  condenser  1  /  2  outlet  temperature  and  common  outlet 
temperature 
0  4     
Anti-freeze alarm in Heat pump mode 
AL 40
Minimum limit of the setpoint in heat pump mode  -50.0 
-58 
AL39 
°C 
°F 
Dec 
int 
AL 41
Maximum limit of the setpoint in heat pump mode 
AL38 
70.0 
158 
°C 
°F 
Dec 
int 
AL 42
Anti-freeze alarm setpoint in heat pump 
Setpoint  temperature  for  low  anti-freeze  alarm,  low  ambient 
temperature (air/air), low temperature air outlet (air/air) 
AL31  AL32  °C/°F  Dec/int 
AL 43
Differential of anti freeze alarm in heat pump mode. To reset the anti-
freeze,  low  ambient  Temperature  (air/air),  low temperature  air  outlet 
(air/air) alarms. 
0.1 
1 
25.0 
45 
°C 
°F 
Dec 
int 
AL 44
Antifreeze  alarm  delay  (low  outlet  temperature  for  air/air  unit)  at  the 
stert up in heat pump mode 
0  250  Sec   
AL 45
Anti-freeze alarm delay for  low air ambient  temperature or  low outlet 
air temperature in heat pump normal condition. 
0  250  Sec   
AL 46
Maximum number of anti-freeze alarm events for low air ambient 
temperature  or  low  outlet  air  temperature  in  heat  pump.  It  sets  the 
alarm reset condition: 
Always manual reset AL46 = 0 
Always automatic reset AL46 = 16 
From automatic to manual reset if AL46 = 1..15 
0  16     
AL 47
Anti-freeze alarm configuration in heat pump 
0= to  turn  the  compressors off  when  the  anti-freeze control  probe  is 
lower  than  AL33  (after  the  time  delay),  the  display  shows  the  alarm 
label. 
Buzzer and Alarm relay are not activated. 
1= to  turn  the  compressors off  when  the  anti-freeze control  probe  is 
lower  than  AL33  (after  the  time  delay),  the  display  shows  the  alarm 
label. 
Buzzer and Alarm relay are activated. 
0  1     
AL 48
Probe selection for antifreeze alarm in heat pump mode 
0= disabled 
1= evaporator inlet temperature 
2= evaporator 1 / 2 outlet temperature 
3=  evaporator  1  /  2  outlet  temperature  and  common  outlet 
temperature 
4= external air temperature 
0  4     
Compressor high discharge temperature 
AL 49
Compressor high discharge temperature setpoint 
0 
0 
150 
302 
°C 
°F 
Dec / 
int 
int 
AL 50
Compressor high discharge temperature differential  0 
0 
25.0 
45 
°C 
°F 
Dec 
int 