Technical data
1592022750 Quick reference guide IC 200CX  Rel. 1.1 25/05/2009 
AL 23
“Evaporator  flow  switch  /  supply  fan  overload” deactivation  time  to 
reset the alarm 
0  250  Sec   
Compressor overload alarm 
AL 24
Compressor overload alarm delay after compressor start-up  0  250  Sec   
AL 25
Maximum number of compressor overload alarm per hour 
Always manual reset if AL20 = 0 
Always automatic reset if AL20 =16 
From automatic to manual reset if AL20 =1..15 
0  16     
AL 26
Enable compressor overload if compressor is deactivated 
0= compressor overload alarm disabled 
1= compressor overload alarm enabled 
0  1     
AL 27
Compressor overload alarm operation 
0= swith off only the compressor 
1= switch off the circuit 
0  1     
Pump down alarm 
AL 28
Maximum  number  of  pump  down  alarm  events  per  hour  in  stop 
condition.  After  this  number  the  alarm  is  logged,  displayed  and 
signalled with alarm relay + buzzer. 
Always manual reset if AL28 = 0 
Always automatic reset if AL28 =16 
From automatic to manual reset if AL28 =1..15 
0  16     
AL 29
Maximum  number  of  pump  down  alarm  events  per  hour  in  start-up 
condition.  After  this  number  the  alarm  is  logged,  displayed  and 
signalled with alarm relay + buzzer. 
Always manual reset if AL29 = 0 
Always automatic reset if AL29 =16 
From automatic to  manual  reset if AL29 =1..15 and  parameter AL30 
config. 
0  16     
AL 30
Select  if  the  pump  down  alarm  must  change  from  automatic  to 
manual reset: 
0= Always automatic reset 
1= Manual reset after AL29 alarm events 
0  1     
Anti-freeze alarm in Chiller mode 
AL 31
Minimum antifreeze setpoint in chiller  -50.0 
-22 
AL32 
°C 
°F 
Dec 
int 
AL 32
Maximum antifreeze setpoint in chiller 
AL31 
70.0 
158 
°C 
°F 
Dec 
int 
AL 33
“Antifreeze / low ambient temperature (air / air unit) / low temperature 
air outlet (air/air)” alarm setpoint temperature 
AL31  AL32  °C/°F  Dec/int 
AL 34
“Antifreeze / low ambient temperature (air / air unit) / low temperature 
air outlet (air/air)” alarm differential temperature 
0.1 
1 
25.0 
45 
°C 
°F 
Dec 
int 
AL 35
Alarm delay for anti-freeze, low ambient air temperature or low outlet 
air temperature 
0  250  Sec   
AL 36
Maximum number anti-freeze, low ambient air temperature or low 
outlet air temperature alarm in chiller 
Always manual reset if AL36 = 0 
Always automatic reset if AL36 = 16 
From automatic to manual if AL36 = 1. .15 
0  16     
AL 37
Anti-freeze alarm configuration in chiller 
0=  when  the  antifreeze  alarm  is  activated  the  compressors  are 
switched off; the display shows the alarm label, the buzzer and alarm 
relay are not activated 
1=  when  the  antifreeze  alarm  is  activated  the  compressors  are 
switched off; the display shows the alarm label, the buzzer and alarm 
relay are activated, the antifreeze heathers are acivated 
0  1     