Technical data
1592022750 Quick reference guide IC 200CX  Rel. 1.1 25/05/2009 
AL 4   
Low pressure alarm differential from analogue input  0.1 
1 
0.0 
0 
25.0 
45 
14.0 
203 
°C 
°F 
bar 
psi 
Dec 
int 
Dec 
Int 
AL 5   
Maximum  number  of  low  pressure  events  from  digital/analogue 
inputs: 
Always manual reset if AL05 = 0 
Always automatic reset if AL05 =16 
From automatic to manual reset if AL05= 1..15 
0  16     
AL 6   
Low temperature/pressure alarm during defrost 
0= Not enabled 
1= Enabled 
0  1     
AL 7   
Low temperature/pressure alarm delay during defrost  0  250  Sec   
AL 8   
Low temperature/pressure alarm with unit in OFF or stand – by: 
0 = Not enabled 
1= Alarm enabled 
0  1     
High Alarm 
AL 9   
High temperature/pressure alarm from analogue input  -50.0 
-58 
0.0 
0 
70.0 
158 
50.0 
725 
°C 
°F 
bar 
psi 
Dec 
int 
Dec 
int 
AL 10
High temperature/pressure alarm differential from analogue input  0.1 
1 
0.0 
0 
25.0 
45 
14.0 
203 
°C 
°F 
bar 
psi 
Dec 
int 
Dec 
int 
Oil Alarm 
AL 11
Low oil pressure / level delay from digital input  0  250  Sec   
AL 12
Minimum time for low oil pressure / level from digital input activation in 
normal working condition. 
0  250  Sec   
AL 13
Maximum number of low oil pressure/level events: 
Always manual reset if AL13= 0 
Always automatic reset if AL13 =16 
From automatic to manual reset if AL13 = 1..15 
0  16     
AL 14
Low oil pressure / oil level when the compressor is OFF 
0= alarm disabled 
1= alarm enabled 
0  1     
Condenser Flow alarm 
AL 15
Condenser water flow configuration 
0= Not enabled 
1= Enabled only in chiller mode 
2= Enabled only in heat pump mode 
3= Enabled in chiller and heat pump mode 
0  3     
AL 16
Condenser flow switch delay after pump activation  0  250  Sec   
AL 17
Flow switch activation time to generate the manual condenser flow 
alarm 
0  250  Sec   
AL 18
Flow switch activation time to generate the automatic condenser flow 
alarm 
0  250  Sec   
AL 19
Flow switch deactivation time to reset the condenser flow alarm  0  250  Sec   
Evaporator Flow alarm 
AL 20
“Evaporator  flow  switch  /  supply  fan  overload”  delay  after  pump 
activation 
0  250  Sec   
AL 21
Flow switch activation time to generate the manual evaporator flow 
alarm 
0  250  Sec   
AL 22
“Evaporator  flow  switch  /  supply  fan  overload”  activation  time  to 
generate the automatic alarm 
0  250  Sec   