Technical data
1592022750 Quick reference guide IC 200CX  Rel. 1.1 25/05/2009 
dF 21
Forced defrost differential  0.1 
1 
0.0 
0 
25.0 
45 
14.0 
203 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
Defrost operative mode 
dF 22
Defrost start-up in unit with 2 circuits 
0= Independent 
1= If both have reached the necessary requirements 
2= If one has reached the necessary requirements 
0  2     
dF 23
End defrost in unit with 2 circuits and common ventilation 
0= Independent 
1= If both have reached the necessary end defrost requirements 
2= If one has reached the necessary end defrost requirements 
0  2     
Start / stop defrost from analog input 
Param
eters 
description  min  max  udm  resolut
ion 
dF 24
Start / stop defrost probe 
0= start and stop with condenser temperature / pressure probe 
1=  start  with  evaporator  pressure  probe  /  stop  with  condenser 
temperature / pressure probe 
2=  start  with  condenser  temperature /  pressure    probe  /  stop with 
evaporator pressure probe 
3= start and stop with evaporator pressure probe 
0  3     
Supply fan functioning during defrost cycle 
dF 25
Set point to enable defrost with condenser fan 
-50.0 
-58 
70.0 
158 
°C 
°F 
Dec 
int 
Defrost with condenser fan 
dF 26
Supply fan status during the defrost cycle 
0= Enabled 
1= Not enabled 
0  1     
Minimum temperature water outlet during defrost 
dF 27
Probe selection for minimum temperature outlet during defrost  0  6     
dF 28
Set point for minimum temperature outlet during defrost 
-50.0 
-58 
0.0 
0 
70.0 
158 
50.0 
725 
°C 
°F 
bar 
psi 
Dec 
int 
Dec 
int 
Pr1 
Password  0  999     
Pr2 
Password  0  999     
Pr3 
Password  0  999     
Alarms 
Param
eters 
Description  min  max  m. u.  Resolu
tion 
Low alarm 
AL 1   
Low pressure alarm delay from analog and digital input  0  250  Sec   
AL 2   
Low  pressure  alarm  delay  if  the  low  pressure  switch  is  used  for  the 
pump down. 
AL02= 0 low pressure alarm not enable during compressor switching 
off from pump down and if compressor OFF 
AL02≠  0  low  pressure  alarm  enable  after  AL02  (starting  from 
compressor switch off) time with compressor OFF 
0  250  Sec  10 Sec 
AL 3   
Low pressure alarm setpoint from analogue input  -50.0 
-58 
0.0 
0 
70.0 
158 
50.0 
725 
°C 
°F 
bar 
psi 
Dec 
int 
Dec 
int 